Mechanical Specifications (continued)
Alarm Terminals, Standard | Quantity: | 6 contacts per side for NO or NC pow- |
|
| er and breaker (fuse) alarms |
| Type: | Cage clamp (WAGO style) |
| Wire Size: | |
|
| |
Input Test Points (each side): | ||
| meter volts: |
|
Standard Test Points | VDC |
|
Optional Test Points1 | AMPS, where 1mV scale = 16A | |
Electrical Specifications |
|
|
|
| |
Operating Voltages | ||
|
|
|
Maximum Input Interruption Device | 800A per feed |
|
|
|
|
Maximum Continuous Input Load | 600A per feed per panel |
|
|
| |
Maximum Output Interruption Device | 100A per | |
| 150A per | |
|
| |
Maximum Continuous Output Load | 80A per | |
| 120A per | |
|
|
|
Max. Voltage Drop | .25Vdc |
|
|
|
|
Max. surface temperature of breakers at | 37°C (99°F) |
|
26°C (79°F) ambient |
|
|
|
| |
Max. panel heat dissipation at full load | 225W/m2 per meter (20.9W/ft2/ft) | |
Percentage of full load heat dissipation | Less than 0.5% |
|
|
|
|
Alarm Relay Contacts | 2A @ 30 Vdc |
|
| 0.6A @ 60 VDC |
|
|
|
|
Max. Alarm Card Power Rating | @20V: 35 mA (0.70 W) |
|
| @20V: 35 mA (0.70 W) |
|
| @24V: 44 mA (1.06 W) |
|
| @27V: 48 mA (1.30 W) |
|
| @30V: 51 mA (1.53 W) |
|
| @42V: 59 mA (2.48 W) |
|
| @48V: 64 mA (3.07 W) |
|
| @56V: 69 mA (3.86 W) |
|
| @60V: 73 mA (4.38 W) |
|
|
|
|
Physical/Environmental |
|
|
|
|
|
Weight, Shipping | ~150 lb (~70 kg) |
|
|
|
|
Weight Without Packaging or Breakers | 63 lb (29 kg) |
|
|
| |
Rack Mounting | 19 in. (482.6 mm), EIA/WECO | |
| 23 in. (584.2 mm), EIA/WECO | |
|
| |
Operating Temperature Range | ||
|
| |
Storage Temperature Range | ||
|
|
|
Humidity |
| |
|
|
|
1. Requires an optional shunt. |
|
|
Telect, Inc. • USA +1.509.926.6000 • Mexico +1.52.33.3836.3700 |
|
Poland +1.48.713.239.100 • UK +1.44.1489.889500 • www.telect.com | Page |
Copyright © 2002 Telect, Inc., All Rights Reserved |