1. Description
DUAL 600A BDFB / BDCBB
Telect’s Dual 600A Battery Distribution Fuse Board / Circuit Breaker Board (BDFB / BDCBB), Model
The
The front panel contains 18 circuit breaker positions per feed for a total of 36 per panel. Each position accepts a standard “bullet ter- minal” circuit breaker rated up to 100A, with the capability of pairing adjacent breakers for
Telect’s Dual 600A BDFB / BDCBB fits standard 19 in. or 23 in. racks set up for either EIA or WECO mounting. Up to four panels can be arranged in a bay3 to provide up to 2400A per feed (4800A per bay).
— Capabilities
Each Panel
•Dual Feed
•600A (Max.,Continuous) Per Feed
•800A (Max.) Interrupt Device Per Feed
•18 Outputs Per Feed; 36 Outputs Per Panel
Full Bay of Four Panels
•Dual Feed
•2400A (Max., Continuous) Per Feed
•3200A (Max.) Interrupt Device Per Feed
•72 Outputs Per Feed; 144 Outputs Per Bay
— Features
•Suitable for primary or secondary distribution
•Modular design expands capability of rack to as much as 4800A
•Open architecture provides easy input/output cabling
•
•Standard “bullet terminal” circuit breakers (up to 100A per position)
•Breaker shunting allows
•Alarm and BATT monitor overcurrent protection
1.Input current test points require an optional shunt and cabling. Contact telect.com for availability. (See Section 5, Accessories.)
2.Optional removable alarm panels provide digital voltage and current meters. Contact telect.com for availability. (See Section 5, Accessories.)
3.When installing four panels in a bay, prefer a
Telect, Inc. • USA +1.509.926.6000 • Mexico +1.52.33.3836.3700 Poland +1.48.713.239.100 • UK +1.44.1489.889500 • www.telect.com
Copyright © 2002 Telect, Inc., All Rights Reserved • Telect Publication