— C. Install Intrabay & Interbay Cabling
The input
— D. Install Alarm Cabling
External indicators (monitors) can be connected to the BDFB / BDCBB alarm board. The external indicators can be wired to accept either a normally open or closed circuit when the VDC PWR or FUSE ALM LEDs or other optional alarms are activated.
To connect power- and
1.Refer to the following illustration and then remove four Phillips screws (screws with
2.Carefully pull off and turn alarm panel cover around.
3.Strip off ¼ in. of insulation on end of a pair of
4.Select a common (C) contact and either a normally closed (NC) or normally open (NO) contact for each alarm desired:
•For a C and NC pair, expect continuity (0 Ω) during normal operation and an open circuit (∞ Ω) for an alarm condition such as an open breaker or a power failure.
•For C and NO pair, expect an open circuit (∞ Ω) during normal operation and continuity (0 Ω) for an alarm condition such as an open breaker or a power failure.