Model 200EU-NOy Option Manual Addendum

SECONDARY MENU (The fixed characteristics of the system).

PRESS

DISPLAY

ACTION

SEL hold until

p-n1

SET TO 0 – REVERSE ACTION

SEL hold until

p-n2

SET TO 2 = TYPE J THERMOCOUPLE

SEL

p-dFDIGITAL FILTER

SET TO 5

SEL

P-SLLOWER LIMIT

SET TO -40 (-40ºC)

SEL

P-SUUPPER LIMIT

SET TO 350 (350ºC)

SEL

P-AH ALARM

SET TO 0

SEL

P-AnHYTERESIS

SET TO 5

SEL

P-dPPROG DECIMAL

SET TO 0

SEL

PVOF PROCESS OFFSET

LEAVE AT 0

SEL

SVOF SET POINT OFFS

LEAVE AT 0

SEL

P-F

SET TO 0 (0 = oC, 1 = oF)

SEL

P-n1

ALREADY CONFIGURED

SEL hold until RETURNS TO MAIN MENU

 

SEL

PV/SV

SET DISPLAY TO 315 C

SEL hold until

P PROP BAND

ALREADY CONFIGURED

SEL

SCROLL TO A7

SET TO 1 (AUTOTUNE )

34

05386 Rev. D

Page 38
Image 38
Teledyne 05386D manual AH Alarm