|
| Flue Gas Analysis System | Installation 3 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
3.1.3 Alarm and/or Control Circuitry
Models having a
The SPDT form "C" (NC/C/NO) contacts of the relay (or relays) are available on the terminal strip within the oxygen analyzer. To properly use the switch that the relay contacts represent, the customer must determine when the relay (or relays) is energized (above or below the setpoint). The appropriate terminal strip connections are identified on the interconnection diagram (see Figure 6).
For those not familiar with relay terminology, the terms normally open (NO) and normally closed (NC) refer to the relay contact configura- tion when the relay is in a
The load current per relay must be limited to 3 Amperes
tive.
3.1.4 Output Signal Current
Instruments which include the designation "I" as part of their model number are equipped with an
Aseparate 1/4 ampere
The range for current output is:
•
Suitable for devices with
The appropriate terminal strip connections are identified on the interconnection diagram (see Figure 6).
TELEDYNE BROWN ENGINEERING |
Analytical Instruments