Thermo Products 100n, chx-3 75n, 125n operation manual Maximum Quantity of Elbows

Models: 125n 100n chx-3 75n

1 67
Download 67 pages 17.21 Kb
Page 16
Image 16
Maximum Quantity of Elbows

All installations and services must be performed by qualified service personnel.

5.All horizontal runs of exhaust vent pipe shall slope upward at least ¼ inch per foot from the outlet of the furnace (for model CHX3), or the outlet of the drain tee (for the model CDX3), to the vent termination, beyond the outside wall. This slope will permit proper drainage of the condensate. Horizontal runs of air intake pipe shall slope downward at least ¼ inch per foot from the outlet of the last elbow or last horizontal run, before exiting the wall, to the intake termination beyond the outside wall. This slope will permit proper drainage of any precipitation that enters the intake pipe.

6.The exhaust vent pipe shall be supported at every joint (no more than 4-feet between supports) to prevent pipe blockage due to condensate trapped at a local low point, or sag, in the vent system.

7.The maximum permissible length of piping (consisting of a combination of straight pipe and a corresponding number of elbows) permitted is:

75 equivalent feet, for the exhaust vent system, and

70 equivalent feet, for the combustion air intake system.

8.The maximum quantity of Schedule 40 series, type DWV thermoplastic pipe elbows allowed in each system is listed in Table 2. When counting pipe elbows, all elbows used in the exhaust vent or combustion air intake systems must be considered. This includes all elbows, or equivalent pipe fittings, used inside the furnace jacket in addition to those used to construct the termination. Furthermore, a credit of 5-feet of straight pipe may be taken for each elbow, up to maximum of three (3) elbows, which is dropped from the maximum permissible number for each system.

Table 2: Maximum Permissible Exhaust Vent and Combustion Air Intake Lengths When Using the

Maximum Quantity of Elbows

Thermoplastic

 

2 in. Diameter IPS

 

3 in. Diameter IPS

 

Pipe Vent Size

 

 

 

(Nominal)

 

 

 

 

 

 

 

 

Exhaust or

Maximum Qty.

Maximum

Exhaust or

Maximum Qty.

 

Maximum

Furnace Model

Intake

of Exhaust

Qty. of Intake

Intake

of Exhaust

 

Qty. of Intake

 

Straight

Elbows 1, 2

Elbows 2

Straight Pipe

Elbows 1, 2

 

Elbows 2

 

Pipe Length

 

 

Length (ft.)

 

 

 

 

(ft.)

 

 

 

 

 

 

CHX3 / CDX3-75

35

8

7

-

-

 

-

CHX3 / CDX3-100

 

Not Permitted

 

35

8

 

7

CHX3 / CDX3-125

 

 

 

 

 

 

 

Superscripts:

1The drain tee supplied with the model series CHX3 / CDX3 furnaces is considered equivalent to one (1), 90° elbow.

2Two (2) 45° elbows can be substituted for one (1), 90° elbow.

Care should be taken to design the shortest possible intake and exhaust systems. Each system should contain as few elbows as possible to insure the satisfactory operation of the furnace. However, system length should never be less than 8 ft of pipe with two (2), 90 deg. elbows. For best overall operation of the combustion system, we recommend the actual equivalent lengths for both the constructed intake and the exhaust systems have approximately the same value.

9.Use a saw designed to cut thermoplastic pipe. All cuts should be made at right angles to the pipe wall. Smooth jagged edges and remove all burrs and strings. All pipe joints must utilize standard PVC Schedule 40 series, DWV type elbows, couplings, and fittings. Clean all pipe surfaces at connections using a fine abrasive material or approved PVC cleaner (primer). Secure