7
3. Installation
3.2 Environment
To ensure safe and proper operation, ensure that the installation conforms to the
following specifications.
Ensure that the installation location is consistent with the following:
Avoid extreme temperature and humidity. Maximal battery life can be attained
with a recommended temperature range of 15° C to 25° C.
Protect the equipment from moisture.
Space and ventilation requirements must be met. Ensure there is at least 100mm
(4 inch) behind and 50mm (2 inch) on the sides of the UPS for ventilation.
Ensure that the front of the UPS remain supply clear for user access.
The External Battery Cabinets must be installed next to or underneath the UPS.