LIMITATIONS AND EXCLUSIONS
This limited warranty shall not cover the UPS, UPS part, or BATTERY during their respective warranty periods, if the following storage, maintenance, installation, operating conditions are not met throughout the warranty periods (5 conditions below):
VALVE REGUALATED LEAD ACID (VRLA) BATTERIES FOR TOSHIBA
INTERNATIONAL CORPORATION UPSREQUIRED OPERATING
CONDITIONS
1. | Temperature | Annual | Average | Temperature per cell < 32°C | |
Temperature |
| 25°C | |||
|
|
| (89°F) for more than 30 | ||
|
| (77°F) |
|
| |
|
|
|
| days | |
|
|
|
|
| |
2. | Maximum number | Discharge time |
| Maximum Number of | |
of full charge/discharge |
|
|
| Cycles (24 months) | |
cycles | 30 minutes |
|
| 69 | |
|
| 15 minutes |
|
| 86 |
|
| 10 minutes |
|
| 110 |
|
| 5 minutes |
|
| 130 |
VALVE REGUALATED LEAD ACID (VRLA) BATTERIES FOT TOSHIBA INTERNATIONAL CORPORATION UPS
INSTALLATION AND MAINTENANCE CONDITIONS
3. | Storage | While UPS is in transit or storage it must always be in | |
suitable temperature (see condition 1). | |||
|
| ||
4. | External Batteries | Parallel battery string applications must be approved | |
by TIC in writing. | |||
|
| ||
5. | Idle Batteries | User must recharge the batteries if not in use | |
(charged) for more than 6 months. | |||
|
|
34