LIMITATIONS AND EXCLUSIONS

This limited warranty shall not cover the UPS, UPS part, or BATTERY during their respective warranty periods, if the following storage, maintenance, installation, operating conditions are not met throughout the warranty periods (5 conditions below):

VALVE REGUALATED LEAD ACID (VRLA) BATTERIES FOR TOSHIBA

INTERNATIONAL CORPORATION UPSREQUIRED OPERATING

CONDITIONS

1.

Temperature

Annual

Average

Temperature per cell < 32°C

Temperature

 

25°C

 

 

 

(89°F) for more than 30

 

 

(77°F)

 

 

 

 

 

 

days

 

 

 

 

 

2.

Maximum number

Discharge time

 

Maximum Number of

of full charge/discharge

 

 

 

Cycles (24 months)

cycles

30 minutes

 

 

69

 

 

15 minutes

 

 

86

 

 

10 minutes

 

 

110

 

 

5 minutes

 

 

130

VALVE REGUALATED LEAD ACID (VRLA) BATTERIES FOT TOSHIBA INTERNATIONAL CORPORATION UPS

INSTALLATION AND MAINTENANCE CONDITIONS

3.

Storage

While UPS is in transit or storage it must always be in

suitable temperature (see condition 1).

 

 

4.

External Batteries

Parallel battery string applications must be approved

by TIC in writing.

 

 

5.

Idle Batteries

User must recharge the batteries if not in use

(charged) for more than 6 months.

 

 