Settings

Options

Default

Remarks

7) OUTLET SETTING

GROUP 1 / GROUP 2

Option 1

This is a load-shed feature.

 

Option 1: 1 On / 2 On

 

 

 

Option 2: 1 Off / 2 On

 

 

 

Option 3: 1 Off / 2 Off

 

 

 

Option 4: 1 On / 2 Off

 

 

8) BATTERY TEST

TEST?

 

Perform battery test

 

immediately

 

 

 

9) SILENCE SET

ON / OFF

OFF

 

10) BAT CABINET SET

0 EXT B. PACKS

0

Shown options when battery

 

1 EXT B. PACKS

 

cabinets are connected.

 

 

 

 

2 EXT B. PACKS

 

 

 

 

 

Alarm on main connector

 

 

 

connected at wrong polarity

11) SITE FAULT SET

ENABLE / DISABLE

 

or installation to main supply

 

 

 

without group.

 

 

 

 

12) LANGUAGE

ENGLISH

ENGLISH

 

 

GERMAN

 

 

 

FRENCH

 

 

 

SPANISH

 

 

 

ITALIAN

 

 

 

 

 

If ON, UPS will work with a

 

 

 

very large range of voltages

 

 

 

and frequencies, without

13) GENERATOR

ON / OFF

 

switching back and forth

 

from Line mode battery

 

 

 

 

 

 

mode.

 

 

 

 

 

 

 

Option to enable and disable

 

 

 

the RS232 port. USB share

 

 

 

the communication line with

14) RS232 CONTROL

ENABLE / DISABLE

 

RS232. Only one option may

 

be used at a time.

 

 

 

 

 

 

 

Complete the installation entirely before changing the default settings or connecting a load to the UPS.

17

Page 39
Image 39