7.3 Power Range:1000 VA (19” Rack-mount model, LV, 1U & 2U)

General

 

Rated power:

1000 VA at power factor 0.7

Technology:

On-line, double conversion topology with automatic

 

bypass

Input

 

Phase:

Single phase with ground

Bypass Voltage:

96VAC- 138VAC (user selectable)

Input Voltage range:

80VAC- 144VAC

Frequency:

50/60 Hz Auto selection

Frequency window from main supply: 45-65 Hz

Synchronization window:

± 3Hz

Input current:

1000 VA 8.2A

Input Power factor:

0.97

Output

 

Output Voltage:

100/110/115/120/127 VAC, selectable from LCD panel

Voltage regulation:

± 2%

Voltage distortion:

< 5% THD at full non-linear load, < 3% THD at full

linear load:

 

Frequency regulation:

± 0.25 Hz (battery or free running mode)

Dynamic response:

± 9 % max from 100% to 20 % or from 20% to 100 %

linear load:

 

Overload capacity:

100-125% 1 min, 125-150% 10 sec

Efficiency:

greater than 86%

Environmental

 

Ambient temperature:

+0 °C to +40 °C

Recommended temperature:

+15 °C to +25 °C

Storage temperature:

-15 °C to +50 °C

Cooling:

Forced air-cooling

Humidity:

0-95%, non-condensing

Audible noise:

< 45 db normal and battery mode (1000 ~1200 VA)

28

Page 50
Image 50
Toshiba 1000 Series manual Power Range1000 VA 19 Rack-mount model, LV, 1U & 2U General, Environmental