7.3 Power Range:1000 VA (19” Rack-mount model, LV, 1U & 2U)
General |
|
Rated power: | 1000 VA at power factor 0.7 |
Technology: | |
| bypass |
Input |
|
Phase: | Single phase with ground |
Bypass Voltage: | 96VAC- 138VAC (user selectable) |
Input Voltage range: | 80VAC- 144VAC |
Frequency: | 50/60 Hz Auto selection |
Frequency window from main supply: | |
Synchronization window: | ± 3Hz |
Input current: | 1000 VA 8.2A |
Input Power factor: | 0.97 |
Output |
|
Output Voltage: | 100/110/115/120/127 VAC, selectable from LCD panel |
Voltage regulation: | ± 2% |
Voltage distortion: | < 5% THD at full |
linear load: |
|
Frequency regulation: | ± 0.25 Hz (battery or free running mode) |
Dynamic response: | ± 9 % max from 100% to 20 % or from 20% to 100 % |
linear load: |
|
Overload capacity: | |
Efficiency: | greater than 86% |
Environmental |
|
Ambient temperature: | +0 °C to +40 °C |
Recommended temperature: | +15 °C to +25 °C |
Storage temperature: | |
Cooling: | Forced |
Humidity: | |
Audible noise: | < 45 db normal and battery mode (1000 ~1200 VA) |
28