29
7.4 Power Range 1000-1200 VA (HV)
General
Rated power: 1000 VA, 1200 VA at power factor 0.7
Technology: On-line, double conversion topology with automatic
bypass
Input
Phase: Single phase with ground
Bypass Voltage: 184VAC-265VAC (user selectable)
Input Voltage range: 160VAC-276VAC
Frequency: 50/60 Hz Auto selection
Frequency window from main supply: 45-65 Hz
Synchronization window: ± 2.5Hz
Input current: 1000 VA 4A, 1200 VA 5.2A
Input Power factor: 0.97
Output
Output Voltage: 208/220/230/240 VAC, selectable from LCD panel
Voltage regulation: ± 2%
Voltage distortion: < 5% THD at full non-linear load, < 3% THD at full
linear load
Frequency regulation: ± 0.25 Hz (battery or free running mode)
Dynamic response: ± 9 % max from 100% to 20 % or from 20% to 100 %
linear load
Overload capacity: 100-125% 1 min, 125-150% 10 sec
Efficiency: greater than 86%