27
7. Technical Specifications
7.2 Power Range 1000-1200 VA (LV)
General
Rated power: 1000 VA, 1200 VA at power factor 0.7
Technology: On-line, double conversion topology with automatic
bypass
Input
Phase: Single phase with ground
Bypass Voltage: 96VAC-138 VAC (user selectable)
Input Voltage range: 80VAC-144 VAC
Frequency: 50/60 Hz Auto selection
Frequency window from main supply: 45-65 Hz
Synchronization window: ± 3Hz
Input current: 1000 VA 8.2A, 1200 VA 10.0A
Input Power factor: 0.97
Output
Output Voltage: 100/110/115/120/127 VAC, selectable from LCD panel
Voltage regulation: ± 2%
Voltage distortion: < 5% THD at full non-linear load, < 3% THD at full
linear load
Frequency regulation: ± 0.25 Hz (battery or free running mode)