30
7.5 Power Range 1000 VA (19” Rack-mount model, HV, 1U & 2U)
General
Rated power: 1000 VA at power factor 0.7
Technology: On-line, double conversion topology with automatic
bypass
Input
Phase: Single phase with ground
Bypass Voltage: 184VAC- 265VAC
Input Voltage range: 160VAC-276VAC
Frequency: 50/60 Hz Auto selection
Frequency window from main supply: 45-65 Hz
Synchronization window: ± 3Hz
Input current: 1000 VA 4A
Input Power factor: 0.97
Output
Output Voltage: 208/220/230/240 VAC, selectable from LCD panel
Voltage regulation: ± 2%
Voltage distortion: < 5% THD at full non-linear load, < 3% THD at full
linear load
Frequency regulation: ± 0.25 Hz (battery or free running mode)
Dynamic response: ± 9 % max from 100% to 20 % or from 20% to 100 %
linear load
Overload capacity: 100-125% 1 min, 125-150% 10 sec
Efficiency: greater than 86%
Environmental
Ambient temperature: +0 °C to +40 °C
Recommended temperature:+15 °C to +25 °C
Storage temperature: -15 °C to +50 °C
Cooling: Forced air-cooling
Humidity: 0-95%, non-condensing
Audible noise: < 45 db normal and battery mode (1000 VA)
< 50 db normal and battery mode (1200 VA)
Standard
Safety: EN50091-1-1
Emissions: EN50091-2
Immunity: EN50091-2 B (1000-1200VA)