4.3 Front Panel Settings

Listed below are the default settings of the primary UPS parameters.

Settings

Options

Default

Remarks

1) O/P VOLT SET

100V/110V/115V/120V/127V

120V

120V (FOR LV series)

(Output Voltage Set)

208/220/230/240 Vac

230V

230V (FOR HV series)

2) I/P FREQ SET

±2%

±5%

Input Frequency range

(Input Frequency Set)

±5%

 

in Free Run mode.

 

±7%

 

 

3) I/P BYPASS SET

±10%

+10/-15%

Input Voltage range when

(Input Bypass Setting)

+10% -15%

 

Bypass mode is on.

 

 

 

+15/-20%

 

 

 

 

 

If ON, enable UPS runs on

4) FREE RUN SET

ON / OFF

ON

unsynchronized Mode.

 

 

 

For example, if input

 

 

 

frequency 55Hz, output

 

 

 

frequency will stay at 60Hz.

 

 

 

If OFF, disable UPS runs on

 

 

 

unsynchronized mode.

 

 

 

For example, if input

 

 

 

frequency 55Hz, UPS will go

 

 

 

to Battery mode.

 

 

 

 

 

 

 

If ON, enable UPS runs on

 

 

 

high efficiency mode.

5) HE MODE SET

ON / OFF

OFF

Bypass mode is on when

 

 

 

power flows at 95% or lower.

 

 

 

If OFF, disable UPS runs on

 

 

 

high efficiency mode.

 

 

 

Bypass mode is on when

 

 

 

power flows at 85% or lower.

 

 

 

 

 

 

 

If ON, enable UPS switch to

6) MANUAL BYPASS

ON / OFF

OFF

Bypass mode immediately.

 

 

 

 

16

Page 38
Image 38
Toshiba 1000 Series manual Front Panel Settings, Settings Options Default Remarks