1.4 Power Requirements
1.4 Power Requirements
Use power module designed exclusively for the V Series. Using other power supply may result in operation error or device malfunction.
|
| ITEM |
|
|
|
|
|
|
|
| Specification |
|
|
|
|
|
|
|
|
|
|
| PS691 |
|
| PS693 |
|
| PS694 |
|
| PS632 |
|
| PS652 |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
| Basic | Rated Voltage |
|
|
|
|
| 24VDC |
|
| 100/110VDC |
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| Max. power |
| 160VA(60W) |
| 120VA(50W) |
| 150VA(50W) |
|
| 50W or less |
|
| 50W or less |
| ||||
| function |
|
|
|
|
|
|
|
| |||||||||
| consumption |
| or less |
| or less |
| or less |
|
|
|
|
|
|
| ||||
| Allowable |
|
|
|
|
|
|
|
| |||||||||
|
| voltage range |
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
| Rated |
| 50/60Hz |
|
|
| DC |
|
|
|
| ||||||
|
| frequency |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Retentive |
| 20ms or less |
| 20ms or less |
| 20ms / 1s± |
|
| 1ms or less |
|
| 1ms or less |
| |||
|
| power |
|
|
|
|
|
|
| 30% / 20s± |
|
|
|
|
|
|
| |
|
| interruption |
|
|
|
|
|
|
| 30% or less |
|
|
|
|
|
|
| |
|
| Distortion rate |
| 10% or less of rated input voltage |
|
|
|
| – |
| ||||||||
|
| Inrush current |
|
|
|
|
| 6.5A/10ms or |
|
| 25A or lower |
| ||||||
|
|
|
|
| peak or lower |
| peak or lower |
| peak or lower |
|
| lower of rated |
|
| of rated |
| ||
|
|
|
|
| *1 |
|
| *1 |
|
| *1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
| Ground current |
| 1.5mA or lower |
|
|
|
| – |
| ||||||||
|
| Insulation |
| 10MΩ or higher (between input and each insulation) |
|
|
|
| ||||||||||
|
| resistance |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Withstand |
| 1500VAC/1 min. |
|
|
|
|
|
|
|
|
|
|
| |||
|
| voltage |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| Grounding |
| Grounding resistance 100Ω or less |
|
|
|
|
|
|
| |||||||
|
| Output rating |
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
| less |
|
|
|
| |||||
|
|
|
|
| of 43W or less |
|
| total of 30W |
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| total of 35W |
| or less |
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| or less |
|
|
|
|
|
|
|
|
| |
|
| Protective |
| Over voltage, currnet protection |
|
|
|
|
|
|
|
| ||||||
|
| circuit |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Auxillialy function | Status display |
| POWER (5V output, green) |
| CHARGE*2 |
|
| POWER (5V output, green) |
| |||||||||
RUN contact |
| Dry A contact |
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
| External | Weight |
| 650g or less |
| 600g or less |
|
|
|
|
|
|
|
| ||||
| Line terminal |
| 10 terminals |
| 9 terminals |
| 10 terminals |
|
| 9 terminals |
| |||||||
| unit |
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
| (detachable) |
| (fixed) |
| (detachable) |
|
|
|
|
|
|
|
*1 After instantaneuous power failure of 5 second or longer. *2 Battery initial charge indicator, green/red.
Important
•Do not connect to the same electrical outlet with equipment that has high power consumption or emits noise, such as air conditioner or copier.
•Use of uninterruptible power supply is recommended in order to prevent loss of power and to protect the content of the hard disk in the event of a power failure. The content of the hard disk is not guaranteed if power is lost due to power failure.
6F8C1111 | 7 |