Chapter 4 Maintenance

4.2Periodic Maintenance

Check the following items periodically (once every six month is recommended). Also check these items when the surrounding condition or environment is changed.

Item

Inspection Description

Action

Power supply related

Power supply voltage

AC85 - 132VAC/170 -

 

(measure at the power supply

264VAC

 

terminal of the module)

 

 

Check for loose power supply

Must be secure

 

terminal screws

 

 

Check for damaged cables

Must not be damaged

Installation

Check that the base unit is

Must not be loose

 

securely in place

 

 

Check that each module is

Must not be loose

 

securely in place

 

 

Check for loose connector in

Must not be loose or

 

front of the module and

damaged

 

damaged cables

 

I/O module related

Measure voltage of each I/O

Must be within specification

 

terminal

 

 

Check the input status LED

Must turn ON normally

 

Check the output status LED

Must turn ON normally

 

Check that the I/O terminal is

Must not be loose

 

secure

 

 

Check that the terminal

Must not be loose or touching

 

screws are secure and not

each other

 

touching each other

 

 

Check for damaged cables

Must not be damaged

Environment

Check the temperature,

Must be within installation

 

humidity, vibration, and dust

environment specification

Battery related

C2 built-in Litium battery

Should be replaced after 10

 

 

years by C2 overhaul

 

PS694 battery

Should be replaced

 

 

after 3 years (Ni-Cd battery)

 

 

after 1 year (Ni-MH battery)

 

Other battery

Should be replaced after two

 

 

years

 

Check that the battery

Must be secure

 

connector is connected

 

 

securely

 

WARNING

Do not attempt to disassemble, modify, or repair. This can cause electrocution, fire, or injury. Contact the Toshiba service desk for repair.

32

Computer module C2PU37 User’s Manual

Page 52
Image 52
Toshiba 2000 user manual Periodic Maintenance