6.2 Buffer memory information

6. RAS Information

6.2 Buffer memory information

Various RAS information are stored in the AS311’s buffer memory. These information can be read by READ instruction. When some abnormality has occurred, check these information.

6.2.1Module status

Address 4 of the buffer memory stores the AS311 module status.

4

F

E

D

C

B

A

9

8

7

6

5

4

3

2

1

0

RDY

ERR

0

0

0

0

0

0

 

 

 

Error code

 

 

 

 

Bit F

 

RDY (Ready)

 

1 = operating normally

 

 

 

 

 

 

 

 

0 = under initialization or error state

 

 

Bit E

 

ERR (Error)

 

1 = error state

 

 

 

 

 

 

 

 

0 = no error (normal)

 

 

 

Bit 7-0

 

Error code

 

Shows the detected error item if ERR is 1.

 

 

 

 

 

 

 

See the table below (H00 when normal)

 

 

 

 

 

 

 

 

 

 

 

 

Error

 

Type of error

 

Description

Status

 

 

 

code

 

 

 

 

 

 

 

 

H01

CPU error

CPU error has been detected

Operation is stopped.

 

 

 

 

 

 

during initialization.

 

 

 

 

H02

ROM error

ROM error has been detected

Operation is stopped.

 

 

 

 

 

 

during initialization.

 

 

 

 

H03

RAM error

Work RAM error has been

Operation is stopped.

 

 

 

 

 

 

detected during initialization.

 

 

 

 

H04

Buffer memory

Buffer memory error has been

Operation is stopped.

 

 

 

 

error

detected during initialization.

 

 

 

 

H05

Switch setting

Switch setting abnormality has

Operation is stopped.

 

 

 

 

abnormal

been detected during

 

 

 

 

 

 

 

initialization.

 

 

 

 

H10

Watchdog

Watchdog timer error has

Operation is stopped.

 

 

 

 

timer error

occurred during operation.

Cold reset will be

 

 

 

 

 

 

 

 

effective.

 

 

 

H11

Trap interrupt

Trap interrupt has occurred by

Operation is stopped.

 

 

 

 

error

detecting illegal instruction

Cold reset will be

 

 

 

 

 

 

during operation.

effective.

 

 

 

H12

Buffer memory

Buffer memory time-out has

Operation is stopped.

 

 

 

 

time-out error

occurred during operation.

Cold reset will be

 

 

 

 

 

 

 

 

effective.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

User’s Manual 53