1. AS311 Overview

1. AS311 Overview

1.1 Introduction

The ASCII interface module AS311 (hereafter called AS311) is a general purpose data communication module for Toshiba’s Programmable Controller PROSEC-T3 (hereafter called T3). By using the AS311, T3 can communicate with external devices, such as a micro computer, bar code reader, printer, display device, sensor, etc., through the serial interface RS-232C or RS-422.

The AS311 has two ports of the serial interface. One port (channel 1) can be selected either RS-232C or RS-422 by switch setting. The other port (channel 2) is RS-232C interface. These two ports can be used independently for data receiving and transmitting.

The transmission is asynchronous (start-stop system).

ASCII is used as the transmission data code.

The figure below shows the typical system configuration.

T3

AS311

Channel 1

RS-232C or RS-422

 

Channel 2

CPU module

RS-232C

NOTE

The maximum number of AS311 that can be controlled by one T3 is not limited by

 

software. However, this module consumes maximum 1 A of internal 5 Vdc power.

 

Confirm that the total 5 Vdc consumed current per one power supply module is

 

within the limit (7 A).

 

 

 

 