E6580772

 

 

 

 

 

 

Parameter name

Title

Setting value

 

 

Details

Com. Error

f850

0 to 4

Sets the inverter operation at time of communication error.

selection

 

 

The

action of inverter

will be different depending on the

 

 

 

status (during operation or halt) of the inverter. (Note 2)

 

 

 

0:

During halt

Inverter stops after free run.

 

 

 

 

During operation

Inverter trips.

 

 

 

1:

During halt

Inverter stops after free run.

 

 

 

 

During operation

Inverter stops after free run.

 

 

 

2:

Invalid

(Setting is enabled with F10M

 

 

 

 

 

option connected.)

 

 

 

3:

During halt

Inverter decelerates to stop.

 

 

 

 

During operation

Inverter decelerates to stop.

 

 

 

4:

During halt

Inverter continues to run.

 

 

 

 

During operation

Inverter continues to run.

Com. Error

f851

0 to 1000

Sets

the time until the

communication error is detected.

detecting time

 

 

Setting is done by a unit of ms. (Note 3)

Reset function

f899

0, 1

Resets the inverter station.

 

 

 

0:

No action

 

 

 

 

1: To reset the inverter station. After resetting, setting

 

 

 

 

data returns to 0.

(Note 1) For setting the parameters, never duplicate the station address on the same communication line. PLC rink relay register is automatically allocated according to the setting of the station address. As for the setting of station addresses, consider the allocation of rink relay register that is determined by the other station addresses and the number of words that have been set in the parameters f831 to f836, and f841 to f846.

The maximum setting value for station address is 255, however when 255 is set, only one word of scan data can be set. To set the scan data in its maximum value of 12 words, setting value of the station address should be: 255-(12-1)= 244.

(Note 2) Setting of “free-run stop” is valid when the “operation command mode selection” [cmod] is selected to the optional add-on cassette.

Setting of “deceleration stop” is valid when the “operation command mode selection” [cmod] is selected to the optional add-on cassette or when the “speed setting mode selection” [fmod] is selected to the optional add-on cassette. At the same time the deceleration stop returns the command of run/stop and the speed reference value to 0. Except when the above command setting is selected, inverter cannot be stopped.

Furthermore when the “operation command mode selection” [cmod] is set to other than the optional add-on cassette and when the “speed setting mode selection” [fmod] is selected to the optional add-on cassette, in some cases inverter can not stop running because of the setting of the parameters (zero- speed operation setting). Torque control is valid when the “operation command mode selection” [cmod] is set to the optional add-on cassette, but the inverter operation becomes “free-run stop” at that time.

13

Page 14
Image 14