E6580772③
3. Functional description
In this section, functions added by the installation of this F10M option unit, on top of the standard inverter functions, are described.
3.1 F10M communication function
Through the communication network, drive and stop control and concentrated monitoring control of operation status can be carried out by the programmable controller and industrial computer.
3.1.1 Connection of transmission cable
zSL1, SL2, SG
Transmission path is constructed by the shielded twisted pair cables as shown in the figure below.
Be sure to connect SL1, SL2 and SG mutually to another station. Note that wrong connection will not bring the correct transmission.
zSHD
Connect a shield of twisted pair cable to the transmission terminal SHD of each station and set up a class 3 or equivalent grounding work in an arbitrary station.
zTerminal resistor
Set terminal resistors at both sides of the system for the sake of impedance matching. Connect terminal resistor
(As for the master station (MS), terminal resistor can be combined by connecting L1 and TERM.)
Shielded twisted pair cable
MS
TERM
L1
L2
SG
FG
TLF001Z | TLF001Z | TLF001Z |
|
SL1 | SL1 | SL1 |
|
SL2 | SL2 | SL2 |
|
SG | SG | SG | Terminal resistor |
SHD | SHD | SHD | 120 |
|
Grounding / Earthing
(Grounding / earthing resistance 100 Ω max.)
Connection of communication cable of TOSLINE F10M
Signal name | Name | Detail |
SL1 | Transmitting and receiving data | Positive line |
SL2 | Transmitting and receiving data | Negative line |
SG | Signal ground | Ground of signal line |
•Do not connect a grounding line of the shield and a power line earth of the inverter or so.
•Separate a transmission cable from the main circuit connection wire by more than 200mm.
10