3. Functional description

In this section, functions added by the installation of this F10M option unit, on top of the standard inverter functions, are described.

3.1 F10M communication function

Through the communication network, drive and stop control and concentrated monitoring control of operation status can be carried out by the programmable controller and industrial computer.

3.1.1 Connection of transmission cable

zSL1, SL2, SG

Transmission path is constructed by the shielded twisted pair cables as shown in the figure below.

Be sure to connect SL1, SL2 and SG mutually to another station. Note that wrong connection will not bring the correct transmission.

zSHD

Connect a shield of twisted pair cable to the transmission terminal SHD of each station and set up a class 3 or equivalent grounding work in an arbitrary station.

zTerminal resistor

Set terminal resistors at both sides of the system for the sake of impedance matching. Connect terminal resistor (120Ω-1/2W) between the terminal block SL1 and SL2.

(As for the master station (MS), terminal resistor can be combined by connecting L1 and TERM.)

Shielded twisted pair cable

MS

TERM

L1

L2

SG

FG

TLF001Z

TLF001Z

TLF001Z

 

SL1

SL1

SL1

 

SL2

SL2

SL2

 

SG

SG

SG

Terminal resistor

SHD

SHD

SHD

120 Ω-1/2W

 

Grounding / Earthing

(Grounding / earthing resistance 100 Ω max.)

Connection of communication cable of TOSLINE F10M

Signal name

Name

Detail

SL1

Transmitting and receiving data

Positive line

SL2

Transmitting and receiving data

Negative line

SG

Signal ground

Ground of signal line

Do not connect a grounding line of the shield and a power line earth of the inverter or so.

Separate a transmission cable from the main circuit connection wire by more than 200mm.