E6580772

Continuous operation depends on the status information that was before the communication error happens.

zDisplay of communication error will be [t].

zDisplay of trip will be [err8].

zWhen interrupting a transmission to change the setting of command input, reboot a power supply if necessary, since the data which have been received before the interruption of transmission are stored in the inverter.

zParameter setting of smaller communication number will be valid in case that the same setting values are allocated to the command input setting which are between 1 and 6, and also to the monitor output setting between 1 and 6.

(Note 3) The setting of communication error detection time is relating to the number of stations connected to the communication line. When changing the setting, fully consider the number of connected stations.

„Other parameters

The following parameters reflect the transmitted data in the control of the inverter.

Parameter name

Title

Setting value

Details

Operation

cmod

4

Validates the command sent from the F10M option.

command mode

 

 

Operation such as run/stop from the other station will be

selection

 

 

possible.

Speed setting

fmod

9

Validates the speed reference value from the F10M option.

mode selection

 

 

 

Torque command

f420

9

Validates the torque command value from the F10M option.

selection

 

 

 

Selection of

f422

5

Validates the synchronized torque bias from the F10M

synchronized

 

 

option.

torque bias input

 

 

 

Selection of

f423

5

Validates the tension torque bias from the F10M option.

tension torque

 

 

 

bias input

 

 

 

Load sharing gain

f424

5

Validates the load sharing gain from the F10M option.

input selection

 

 

 

Power running

f440

5

Validates power running torque limit from the F10M option.

torque limit 1

 

 

 

selection

 

 

 

Selection of

f442

5

Validates regenerative torque limit from the F10M option.

regenerative

 

 

 

torque limit 1

 

 

 

14

Page 15
Image 15
Toshiba E6580772 instruction manual „ Other parameters