Toshiba LF414 manual Flow rate indication is not stable, - 46 -, 6F8A0870, Start, resistance?

Models: LF414

1 65
Download 65 pages 63.14 Kb
Page 47
Image 47
7.2.3Flow rate indication is not stable

6F8A0870

7.2.3Flow rate indication is not stable

Is power supply voltage START within the specified range?

Is power supply voltage

NO

within the specified range?

 

YES

 

Are cables securely connected? NO

YES

 

Is the flowmeter grounded

NO

with 100Ωor less ground

 

resistance?

 

YES

 

Is the detector pipe filled

NO

with fluid?

 

Use a power supply within the specified range.
Connect each cable securely to the terminal board.

Ground the flowmeter with a copper braid or wire(5.5 mm² minimum) to a good earth ground.

(100Ωor less ground resistance)

Design piping so that the detector pipe is filled with fluid all the time.

Are cables securely connected? NO YES

Is the fluid carrying bubbles?

NO

YES

Design piping so that the fluid does not carry bubbles.

Is there high-voltage or large current cable or equipment YES near the flowmeter?

NO

Contact your nearest Toshiba representative.

Install the flowmeter away from equipment producing electromagnetic or electro- static interference.

Note 1: If the detector tube is not filled with operating fluid, the flow is indefinite and measurement is impossible. Be sure to fill the detector tube with operating fluid before starting measurement.

- 46 -

Page 47
Image 47
Toshiba LF414 manual Flow rate indication is not stable, - 46 -, 6F8A0870, Start, Is power supply voltage, resistance?