General Data
Table GD-1 — General Data — 10–60Ton Units
| 10Ton | 15Ton | 20Ton | 25Ton | 30Ton | 40Ton | 50Ton | 60Ton |
Model Number | CGA120 | CGA180 | ||||||
Compressor Data |
|
|
|
|
|
|
|
|
Model | Scroll | Scroll | Scroll | Scroll | Scroll | Scroll | Scroll | Scroll |
Quantity | 2 | 2 | 2 | 1/1 | 2 | 4 | 2/2 | 4 |
Nominal Tons per Compressor | 5 | 7.5 | 10 | 10/15 | 15 | 10 | 10/15 | 15 |
Evaporator |
|
|
|
|
|
|
|
|
Nominal Size (Tons) | 10 | 15 | 20 | 25 | 30 | 40 | 50 | 60 |
Water Storage Capacity (Gallons)² | 1.4 | 1.5 | 2.2 | 2.7 | 3.2 | 4.1 | 5.0 | 7.4 |
Min. Flow Rate (GPM) | 12.0 | 18.0 | 24 | 30 | 36 | 48 | 60 | 72 |
Max. Flow Rate (GPM) | 36.0 | 54.0 | 72 | 90 | 108 | 144 | 180 | 216 |
Max EWT At | 100 | 100 | 108 | 108 | 108 | 108 | 108 | 108 |
Condenser |
|
|
|
|
|
|
|
|
Nominal Size (Tons) | 10 | 15 | 20 | 25 | 30 | 40 | 50 | 60 |
Number of Coils | 1 | 2 | 1 | 2 | 2 | 2 | 2 | 2 |
Coil Size (ea., Inches)4 | 28 x 108 | 28 x 83 | 61 x 71 | 45 x 71/35 x 71 | 56 x 70 | 56 x 70 | 57 x 96 | 57 x 96 |
Number of Rows | 2 | 2 | 3 | 3 | 3 | 3 | 3 | 4 |
Subcooler Size (ea., Inches) | 4 x 108 | 4 x 83 | 10 x 71 | 14 x 71 | 9 x 70 | 9 x 70 | 9 x 96 | 9 x 96 |
Condenser Fans |
|
|
|
|
|
|
|
|
Quantity | 1 | 2 | 2 | 3 | 4 | 4 | 6 | 6 |
Diameter (Inches) | 28 | 26 | 26 | 26 | 26 | 26 | 26 | 26 |
CFM (Total) | 8,120 | 11,600 | 15,000 | 21,650 | 29,200 | 29,200 | 42,300 | 40,700 |
Nominal RPM | 1100 | 1100 | 1140 | 1140 | 1140 | 1140 | 1140 | 1140 |
Tip Speed (Ft/Min) | 8060 | 7490 | 7750 | 7750 | 7750 | 7750 | 7750 | 7750 |
Motor HP (ea.) | 1.0 | 1/2 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 |
Drive Type | Direct | Direct | Direct | Direct | Direct | Direct | Direct | Direct |
Minimum Outdoor Air Temperature Permissible |
|
|
|
|
|
|
| |
For Mechanical Cooling¹ |
|
|
|
|
|
|
|
|
Standard Ambient Control Unit (°F) | 50 | 50 | 30 | 30 | 30 | 30 | 30 | 30 |
Standard Ambient w/Hot Gas Bypass (°F) | 60 | 60 | 40 | 40 | 40 | 40 | 40 | 40 |
Low Ambient Option (°F) | 0 | 0 | 0 | 0 | 0 | 0 | 0 | 0 |
Low Ambient Control w/Hot Gas Bypass(°F) 15 | 15 | 10 | 10 | 10 | 10 | 10 | 10 | |
General Unit |
|
|
|
|
|
|
|
|
Unload Steps | ||||||||
No. of Independent Refrig. Circuits | 2 | 2 | 1 | 1 | 1 | 2 | 2 | 2 |
Refrigerant Charge (lbs. R22/Circuit) | 8.25 | 11.5 | 40.5 | 54.0 | 72.0 | 38.0 | 49.0 | 75.00 |
Oil Charge (Pints/Circuit) | 4.1 | 7.5 | 17.0 | 22.3 | 27.6 | 17.0 | 22.3 | 27.6 |
*Unloading steps depend upon which compressor is lead compressor. Notes:
1.Minimum
2.Includes piping internal to chiller.
3.At 95°F ambient.
4.Does not include subcooling portion of coil.