Trane CG-PRC007-EN manual Part Load, Performance, 10-60Ton, Data - 60 HZ

Models: CG-PRC007-EN

1 52
Download 52 pages 16.02 Kb
Page 27
Image 27
Part Load

Performance

(10–60Ton)

Data — 60 HZ

Part Load

 

 

 

 

Table PD-18— Part Load Data,ARI Points (10-60Tons)

 

 

 

 

 

 

Entering Condenser AirTemperature (Degrees F)

 

 

 

 

Model

 

95

86.9

84.5

77.7

77.3

72.5

72.3

71.5

 

Tons

Number

 

100% Load

86% Load

82% Load

71% Load

70% Load

62% Load

62% Load

61% Load

 

 

 

EER

10.0

 

10

CGA 1202

Capacity (Tons)

8.7

 

 

 

KW Input

10.5

 

 

 

EER

9.6

 

15

CGA 180

Capacity (Tons)

13.6

 

 

 

KW Input

16.9

 

 

 

EER

9.8

15.2

 

20

CGAF-C20

Capacity (Tons)

17.7

10.7

 

 

 

KW Input

21.6

8.5

 

 

 

EER

9.8

13.8

 

25

CGAF-C25

Capacity (Tons)

23.1

16.3

 

 

 

KW Input

28.3

14.2

 

 

 

EER

9.8

14.2

 

30

CGAF-C30

Capacity (Tons)

28.0

17.0

 

 

 

KW Input

34.3

14.4

 

 

 

EER

9.7

11.9

15.1

 

40

CGAF-C40

Capacity (Tons)

34.5

28.4

21.4

 

 

 

KW Input

42.7

28.6

17.1

 

 

 

EER

9.7

11.3

13.5

 

50

CGAF-C50

Capacity (Tons)

43.0

37.2

30.6

 

 

 

KW Input

53.2

39.4

27.2

 

 

 

EER

9.7

11.9

15.2

 

60

CGAF-C60

Capacity (Tons)

55.4

45.7

34.6

 

 

 

KW Input

68.6

45.9

27.3

 

Table PD-18 Continued — Part Load Data,ARI Points (10-60Tons) Continued

 

 

 

 

 

 

Entering Condenser AirTemperature (Degrees F)

 

 

Model

 

66.2

65.3

57.4

55

 

Tons

Number

 

52% Load

51% Load

37% Load

32% Load

 

 

 

EER

13.5

 

10

CGA 120

Capacity (Tons)

4.6

 

 

 

KW Input

4.1

 

 

 

EER

13.5

 

15

CGA 180

Capacity (Tons)

7.1

 

 

 

KW Input

6.2

 

 

 

EER

 

 

20

CGAF-C20

Capacity (Tons)

 

 

 

 

KW Input

 

 

 

 

EER

 

15.3

 

25

CGAF-C25

Capacity (Tons)

 

11.7

 

 

 

KW Input

 

9.1

 

 

 

EER

 

 

30

CGAF-C30

Capacity (Tons)

 

 

 

 

KW Input

 

 

 

 

EER

 

17.6

 

40

CGAF-C40

Capacity (Tons)

 

10.9

 

 

 

KW Input

 

7.4

 

 

 

EER

 

17.0

 

50

CGAF-C50

Capacity (Tons)

 

15.9

 

 

 

KW Input

 

11.2

 

 

 

EER

 

18.3

 

60

CGAF-C60

Capacity (Tons)

 

17.8

 

 

 

KW Input

 

11.7

 

Notes:

1.Rated in accordance with ARI Standard 550/590-98

-44 Degrees leaving chilled water temperature

-Constant Evaporator waterflow as determined at full load operation, 95 F ambient, and 10F evaporator temperature drop.

-Entering ambient temperature based on 55F for loads below 33%

-Entering ambient temperature based on 0.60(%load)+35 for loads above 33%

-EER- Energy Efficiency Ratio ( Btu/Watt-hour). Power inputs include compressor, condenser fans and control power.

2.Single phase CGA120B1 model should be re-rated at all operating points using the following factors: 1.08 x KW, 0.92 x EER

CG-PRC007-EN

27

Page 27
Image 27
Trane CG-PRC007-EN manual Performance, Data - 60 HZ, Table PD-18-Part Load Data,ARI Points 10-60Tons