Trane CG-PRC007-EN Performance, 40-60Ton, Data - 50 HZ, Part Load, Table PD-24-40Ton - CGAF-C40

Models: CG-PRC007-EN

1 52
Download 52 pages 16.02 Kb
Page 29
Image 29
Table PD-24— 40Ton — CGAF-C40

Performance

(40–60Ton)

Data — 50 HZ

Part Load

 

 

 

 

Table PD-24— 40Ton — CGAF-C40

 

Percent

 

 

 

Entering Condenser Air Temperature (Degrees F)

 

 

 

 

Load

 

75

85

95

105

115

120

 

 

 

EER

14.2

12.2

10.3

8.7

7.3

6.6

 

 

100

Capacity

32.4

30.9

29.3

27.7

25.9

25.0

 

 

 

System KW

27.4

30.5

34.1

38.2

42.8

45.3

 

 

 

EER

14.9

12.8

10.9

9.2

7.7

7.1

 

 

75

Capacity

25.2

24.0

22.8

21.5

20.2

19.5

 

 

 

System KW

20.3

22.5

25.0

27.9

31.3

33.1

 

 

 

EER

16.3

14.2

12.2

10.4

8.8

8.1

 

 

50

Capacity

17.8

17.1

16.3

15.4

14.5

14.0

 

 

 

System KW

13.2

14.5

16.0

17.7

19.8

20.9

 

 

 

EER

14.3

12.2

10.3

8.6

7.2

6.5

 

 

25

Capacity

8.4

8.0

7.6

7.1

6.7

6.4

 

 

 

System KW

7.1

7.9

8.9

9.9

11.1

11.8

 

Table PD-25— 50Ton — CGAF-C50

Percent

 

 

 

Entering Condenser Air Temperature (Degrees F)

 

 

Load

 

75

85

95

105

115

120

 

EER

14.2

12.3

10.5

9.0

7.5

6.9

100

Capacity

40.4

38.7

36.8

34.8

32.6

31.4

 

System KW

34.3

37.8

41.9

46.6

51.8

54.6

 

EER

14.7

12.8

11.0

9.4

7.9

7.3

80

Capacity

33.4

31.9

30.4

28.7

26.9

26.0

 

System KW

27.3

30.0

33.1

36.7

40.7

42.9

 

EER

15.5

13.6

11.8

10.1

8.6

7.9

60

Capacity

26.2

25.1

24.0

22.7

21.4

20.7

 

System KW

20.2

22.1

24.3

26.9

29.7

31.3

 

EER

14.5

12.6

10.8

9.2

7.7

7.1

30

Capacity

12.4

11.9

11.3

10.7

10.0

9.6

 

System KW

10.3

11.3

12.6

14.0

15.5

16.4

Table PD-26— 60Ton — CGAF-C60

Percent

 

 

 

Entering Condenser Air Temperature (Degrees F)

 

 

Load

 

75

85

95

105

115

120

 

EER

14.1

12.2

10.4

8.8

7.4

6.7

100

Capacity

52.2

49.8

47.3

44.5

41.6

40.1

 

System KW

44.4

49.2

54.6

60.8

67.7

71.4

 

EER

14.9

12.9

11.0

9.4

7.9

7.2

75

Capacity

40.5

38.7

36.7

34.6

32.4

31.2

 

System KW

32.7

36.1

40.0

44.4

49.3

52.0

 

EER

16.2

14.2

12.3

10.5

8.9

8.2

50

Capacity

28.6

27.4

26.1

24.7

23.3

22.5

 

System KW

21.2

23.2

25.5

28.2

31.2

32.9

 

EER

15.5

13.4

11.5

9.8

8.2

7.5

25

Capacity

13.8

13.2

12.5

11.8

11.1

10.7

 

System KW

10.6

11.8

13.0

14.5

16.1

17.0

Notes:

1.Data based on 0.0001 fouling factor at sea level.

2.Interpolation between points is permissible.

3.Extrapolation beyond points is not permissible.

4.EER - Energy Efficiency Ratio (Btu/watt-hour). Power inputs include compressors, condenser fans and control power

5.Ratings based on evaporator drop of 10°F

6.Rated in accordance with ARI Standard 550/590-98.

7.Data obtained assuming 400 Volt supply.

CG-PRC007-EN

29

Page 29
Image 29
Trane CG-PRC007-EN manual Performance, 40-60Ton, Data - 50 HZ, Part Load, Table PD-24-40Ton - CGAF-C40