Performance | |
Data — 50 HZ | Part Load |
|
|
|
|
Table PD-19 — 10Ton — CGA 120
Percent |
|
|
| Entering Condenser Air Temperature (Degrees F) |
|
| |
Load |
| 75 | 85 | 95 | 105 | 115 | 120 |
| EER | 13.9 | 11.9 | 10.2 | 8.6 | 7.3 | 6.7 |
100 | Capacity | 8.1 | 7.7 | 7.3 | 6.9 | 6.5 | 6.3 |
| System KW | 13.9 | 15.5 | 17.3 | 19.3 | 21.6 | 22.9 |
| EER | 11.6 | 10.1 | 8.7 | 7.4 | 6.3 | 5.8 |
50 | Capacity | 3.7 | 3.5 | 3.4 | 3.1 | 3.0 | 2.9 |
| System KW | 3.8 | 4.2 | 4.6 | 5.1 | 5.7 | 6.0 |
Table PD-20 — 15Ton — CGA 180
Percent |
|
|
| Entering Condenser Air Temperature (Degrees F) |
|
| |
Load |
| 75 | 85 | 95 | 105 | 115 | 120 |
| EER | 13.8 | 11.7 | 9.7 | 8.1 | 6.6 | 6.0 |
100 | Capacity | 12.6 | 12.0 | 11.4 | 10.7 | 10.0 | 9.7 |
| System KW | 11.0 | 12.4 | 14.0 | 15.9 | 18.1 | 19.3 |
| EER | 12.5 | 10.7 | 8.9 | 7.4 | 6.1 | 5.5 |
50 | Capacity | 5.8 | 5.5 | 5.3 | 4.9 | 4.6 | 4.5 |
| System KW | 5.5 | 6.3 | 7.1 | 8.1 | 9.1 | 9.7 |
Table PD-21 — 20Ton — CGAF-C20
Percent |
|
|
| Entering Condenser Air Temperature (Degrees F) |
|
| |
Load |
| 75 | 85 | 95 | 105 | 115 | 120 |
| EER | 14.3 | 12.3 | 10.4 | 8.8 | 7.3 | 6.7 |
100 | Capacity | 16.6 | 15.8 | 15.0 | 14.2 | 13.2 | 12.8 |
| System KW | 13.9 | 15.5 | 17.3 | 19.3 | 21.6 | 22.9 |
| EER | 16.2 | 14.1 | 12.2 | 10.4 | 8.8 | 8.0 |
50 | Capacity | 8.9 | 8.5 | 8.1 | 7.7 | 7.2 | 7.0 |
| System KW | 6.6 | 7.2 | 8.0 | 8.9 | 9.9 | 10.4 |
Table PD-22 — 25Ton — CGAF-C25
Percent |
|
|
|
| Entering Condenser Air Temperature (Degrees F) |
|
| |
Load |
|
| 75 | 85 | 95 | 105 | 115 | 120 |
| EER | 14.2 | 12.3 | 10.6 | 9.0 | 7.6 | 7.0 | |
100 | Capacity | 21.7 | 20.7 | 19.7 | 18.6 | 17.4 | 16.8 | |
| System KW | 18.3 | 20.1 | 22.3 | 24.8 | 27.5 | 29.0 | |
| EER | 15.7 | 13.7 | 11.9 | 10.2 | 8.7 | 7.9 | |
60 | Capacity | 13.8 | 13.2 | 12.6 | 11.9 | 11.2 | 10.8 | |
| System KW | 10.6 | 11.6 | 12.7 | 14.1 | 15.6 | 16.4 | |
| EER | 15.7 | 13.8 | 12.0 | 10.3 | 8.8 | 8.1 | |
40 | Capacity | 9.4 | 9.0 | 8.6 | 8.2 | 7.7 | 7.4 | |
| System KW | 7.2 | 7.9 | 8.6 | 9.5 | 10.5 | 11.1 | |
Table |
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |
Percent |
|
|
|
| Entering Condenser Air Temperature (Degrees F) |
|
| |
Load |
|
| 75 | 85 | 95 | 105 | 115 | 120 |
| EER | 14.3 | 12.4 | 10.6 | 9.1 | 7.7 | 7.0 | |
100 | Capacity | 26.2 | 25.1 | 23.9 | 22.6 | 21.2 | 20.5 | |
| System KW | 22.0 | 24.3 | 27.0 | 29.9 | 33.3 | 35.1 | |
| EER | 15.2 | 13.4 | 11.7 | 10.0 | 8.6 | 7.9 | |
50 | Capacity | 14.0 | 13.4 | 12.8 | 12.1 | 11.4 | 11.0 | |
| System KW | 11.1 | 12.0 | 13.2 | 14.5 | 16.0 | 16.8 |
Notes:
1.Data based on 0.0001 fouling factor at sea level.
2.Interpolation between points is permissible.
3.Extrapolation beyond points is not permissible.
4.EER - Energy Efficiency Ratio
5.Ratings based on evaporator drop of 10°F
6.Rated in accordance with ARI Standard
7.Data obtained assuming 400 Volt supply.