Trane CG-PRC007-EN manual 10-30Ton, Data - 50 HZ, Performance, Full Load, Table PD-10-10Ton - CGA

Models: CG-PRC007-EN

1 52
Download 52 pages 16.02 Kb
Page 25
Image 25
(10–30Ton)

Performance

(10–30Ton)

Data — 50 HZ

Full Load

 

 

 

 

Table PD-10— 10Ton — CGA 120

 

 

 

 

 

 

 

 

 

Entering Condenser Air Temperature (Degree F)

 

 

 

 

 

 

 

 

 

 

85.0

 

 

 

95.0

 

 

 

105.0

 

 

 

115.0

 

 

 

120.0

 

LWT

Percent

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

(Deg F)

Glycol

 

(Tons)

KW

EER

 

(Tons)

KW

EER

(Tons)

KW

EER

 

(Tons)

KW

EER

 

(Tons)

KW

EER

40

0

7.2

7.6

11.4

6.8

8.4

9.7

 

6.4

9.4

8.2

6.0

10.5

6.9

5.8

11.1

6.3

42

0

7.4

7.6

11.7

7.1

8.5

10.0

 

6.7

9.5

8.4

6.3

10.6

7.1

6.1

11.2

6.5

44

0

7.7

7.7

12.0

7.3

8.6

10.2

 

6.9

9.6

8.7

6.5

10.7

7.3

6.3

11.3

6.7

45

0

7.9

7.8

12.1

7.5

8.7

10.3

 

7.1

9.7

8.8

6.6

10.8

7.4

6.4

11.4

6.8

46

0

8.0

7.9

12.2

7.6

8.7

10.5

 

7.2

9.7

8.9

6.8

10.8

7.5

6.6

11.4

6.9

48

0

8.3

8.0

12.5

7.9

8.8

10.7

 

7.5

9.8

9.1

7.0

10.9

7.7

6.8

11.5

7.1

50

0

8.6

8.1

12.8

8.2

9.0

11.0

 

7.7

10.0

9.3

7.3

11.1

7.9

7.1

11.7

7.3

Table PD-11— 15Ton — CGA 180

 

 

 

 

 

 

 

 

 

Entering Condenser Air Temperature (Degree F)

 

 

 

 

 

 

 

 

 

 

 

85.0

 

 

 

95.0

 

 

 

105.0

 

 

 

115.0

 

 

 

120.0

 

 

LWT

Percent Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

(Deg F)

Glycol

(Tons)

KW

EER

 

(Tons)

KW

EER

(Tons)

KW

EER

 

(Tons)

KW

EER

(Tons)

KW

EER

 

40

0

 

11.2

12.1

11.1

10.6

13.8

9.2

 

10.0

15.7

7.6

9.3

17.8

6.2

 

8.9

19.0

5.6

 

42

0

 

11.6

12.2

11.4

11.0

13.9

9.5

 

10.3

15.8

7.9

9.6

17.9

6.4

 

9.3

19.1

5.8

 

44

0

 

12.0

12.4

11.7

11.4

14.0

9.8

 

10.7

15.9

8.1

10.0

18.1

6.6

 

9.7

19.3

6.0

 

45

0

 

12.2

12.4

11.8

11.6

14.1

9.9

 

10.9

16.0

8.2

10.2

18.2

6.8

 

9.9

19.4

6.1

 

46

0

 

12.5

12.5

12.0

11.8

14.1

10.1

11.2

16.1

8.3

10.4

18.2

6.9

 

10.1

19.4

6.2

 

48

0

 

12.9

12.6

12.3

12.3

14.3

10.3

11.6

16.2

8.6

10.8

18.4

7.1

 

10.5

19.6

6.4

 

50

0

 

13.4

12.7

12.6

12.7

14.4

10.6

12.0

16.3

8.8

11.2

18.5

7.3

 

10.9

19.7

6.6

 

Table PD-12 — 20Ton — CGAF-C20

 

 

 

 

 

 

 

 

 

Entering Condenser Air Temperature (Degree F)

 

 

 

 

 

 

 

 

 

 

85.0

 

 

 

95.0

 

 

 

105.0

 

 

 

115.0

 

 

 

120.0

 

LWT

Percent

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

(Deg F)

Glycol

 

(Tons)

KW

EER

 

(Tons)

KW

EER

(Tons)

KW

EER

 

(Tons)

KW

EER

 

(Tons)

KW

EER

40

0

14.7

15.2

11.7

14.0

17.0

9.9

 

13.2

19.0

8.3

12.3

21.3

6.9

11.9

22.5

6.3

42

0

15.3

15.3

12.0

14.5

17.1

10.2

 

13.7

19.2

8.6

12.8

21.5

7.1

12.3

22.7

6.5

44

0

15.8

15.5

12.3

15.0

17.3

10.4

 

14.2

19.3

8.8

13.2

21.6

7.3

12.8

22.9

6.7

45

0

16.1

15.5

12.4

15.3

17.3

10.6

 

14.4

19.4

8.9

13.5

21.7

7.4

13.0

23.0

6.8

46

0

16.4

15.6

12.6

15.5

17.4

10.7

 

14.7

19.5

9.0

13.7

21.8

7.5

13.2

23.1

6.9

48

0

16.9

15.7

12.9

16.1

17.6

11.0

 

15.2

19.7

9.3

14.2

22.0

7.8

13.7

23.3

7.1

50

0

17.5

15.9

13.2

16.6

17.8

11.2

 

15.7

19.9

9.5

14.7

22.2

8.0

14.2

23.5

7.3

Table PD-13 — 25Ton — CGAF-C25

 

 

 

 

 

 

 

 

 

Entering Condenser Air Temperature (Degree F)

 

 

 

 

 

 

 

 

 

 

85.0

 

 

 

95.0

 

 

 

105.0

 

 

 

115.0

 

 

 

120.0

 

LWT

Percent

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

(Deg F)

Glycol

 

(Tons)

KW

EER

 

(Tons)

KW

EER

(Tons)

KW

EER

 

(Tons)

KW

EER

 

(Tons)

KW

EER

40

0

19.3

19.8

11.7

18.3

21.9

10.0

 

17.3

24.3

8.5

16.2

27.0

7.2

15.6

28.5

6.6

42

0

20.0

20.0

12.0

19.0

22.1

10.3

 

17.9

24.5

8.8

16.8

27.3

7.4

16.2

28.7

6.8

44

0

20.7

20.1

12.3

19.7

22.3

10.6

 

18.6

24.8

9.0

17.4

27.5

7.6

16.8

29.0

7.0

45

0

21.1

20.2

12.5

20.1

22.4

10.7

 

18.9

24.9

9.1

17.7

27.6

7.7

17.1

29.1

7.1

46

0

21.5

20.3

12.7

20.4

22.5

10.9

 

19.3

25.0

9.3

18.1

27.7

7.8

17.4

29.2

7.2

48

0

22.2

20.5

13.0

21.1

22.7

11.2

 

20.0

25.2

9.5

18.7

28.0

8.0

18.1

29.4

7.4

50

0

23.0

20.7

13.3

21.9

22.9

11.4

 

20.7

25.4

9.8

19.4

28.2

8.3

18.7

29.7

7.6

Table PD-14 — 30Ton — CGAF-C30

 

 

 

 

 

 

 

 

 

 

Entering Condenser Air Temperature (Degree F)

 

 

 

 

 

 

 

LWT

Percent

 

85.0

 

 

 

95.0

 

 

 

105.0

 

 

 

115.0

 

 

 

120.0

 

 

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

(Deg F)

Glycol

 

(Tons)

KW

EER

 

(Tons)

KW

EER

 

(Tons)

KW

EER

 

(Tons)

KW

EER

 

(Tons)

KW

EER

 

40

0

23.4

23.9

11.7

22.2

26.5

10.1

21.0

29.5

8.6

19.7

32.8

7.2

19.0

34.6

6.6

42

0

24.2

24.1

12.1

23.1

26.7

10.4

21.8

29.7

8.8

20.5

33.0

7.4

19.7

34.8

6.8

44

0

25.1

24.3

12.4

23.9

27.0

10.6

22.6

29.9

9.1

21.2

33.3

7.7

20.5

35.1

7.0

45

0

25.6

24.4

12.6

24.3

27.1

10.8

23.0

30.1

9.2

21.6

33.4

7.8

20.9

35.2

7.1

46

0

26.0

24.5

12.7

24.8

27.2

10.9

23.4

30.2

9.3

22.0

33.5

7.9

21.3

35.3

7.2

48

0

26.9

24.7

13.1

25.7

27.4

11.2

24.3

30.4

9.6

22.8

33.8

8.1

22.0

35.6

7.4

50

0

27.9

24.9

13.4

26.5

27.6

11.5

25.1

30.7

9.8

23.6

34.0

8.3

22.8

35.9

7.6

Notes:

1.Data based on 0.0001 fouling factor at sea level.

2.Interpolation between points is permissible.

3.Extrapolation beyond points is not permissible.

4.EER - Energy Efficiency Ratio (Btu/watt-hour). Power

inputs include compressors, condenser fans and control power.

5.Ratings based on evaporator drop of 10°F.

6.Rated in accordance with ARI Standard 550/590-98

7.Minimum recommended ethylene glycol percentage used for leaving water temperatures below 40°.

8.Data obtained assuming 400 Volt Supply.

9.Use the following equation to calculate COP values at other than ARI conditions, COP = EER x .2928.

CG-PRC007-EN

25

Page 25
Image 25