Trane CG-PRC007-EN 50-60Ton, Performance, Data - 60 HZ, Full Load, Table PD-7-50Ton - CGAF-C50

Models: CG-PRC007-EN

1 52
Download 52 pages 16.02 Kb
Page 24
Image 24
(50–60Ton)
Table PD-9 — Coefficient of Performance (COP) and Integrated Part LoadValues (IPLV) at ARI Conditions

Performance

(50–60Ton)

Data — 60 HZ

Full Load

 

 

 

 

Table PD-7— 50Ton — CGAF-C50

 

 

 

 

 

 

 

 

Entering Condenser Air Temperature (Degree F)

 

 

 

 

 

 

 

 

 

 

75.0

 

 

 

85.0

 

 

 

95.0

 

 

 

105.0

 

 

 

115.0

 

 

LWT

Percent Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

(Deg F)

Glycol

(Tons)

KW

EER

 

(Tons)

KW

EER

(Tons)

KW

EER

(Tons)

KW

EER

 

(Tons)

KW

EER

20

28

28.5

39.7

8.6

27.1

43.4

7.5

 

25.6

47.7

6.4

 

24.1

52.6

5.5

22.5

58.2

4.6

 

25

24

31.9

40.5

9.4

30.4

44.3

8.2

 

28.7

48.7

7.1

 

27.1

53.8

6.0

25.3

59.5

5.1

 

30

19

35.6

41.4

10.3

33.9

45.3

9.0

 

32.1

49.8

7.7

 

30.3

55.0

6.6

28.4

60.7

5.6

 

35

14

39.5

42.4

11.2

37.7

46.4

9.7

 

35.8

51.0

8.4

 

33.8

56.2

7.2

31.7

62.0

6.1

 

40

0

44.1

43.5

12.2

42.1

47.6

10.6

40.0

52.3

9.2

 

37.8

57.6

7.9

35.5

63.5

6.7

 

42

0

45.7

43.9

12.5

43.6

48.0

10.9

41.5

52.7

9.4

 

39.2

58.1

8.1

36.9

64.1

6.9

 

44

0

47.4

44.3

12.8

45.3

48.4

11.2

43.0

53.2

9.7

 

40.7

58.6

8.3

38.3

64.6

7.1

 

45

0

48.2

44.5

13.0

46.1

48.7

11.4

43.8

53.5

9.8

 

41.5

58.9

8.5

39.0

64.9

7.2

 

46

0

49.1

44.7

13.2

46.9

48.9

11.5

44.6

53.7

10.0

42.2

59.1

8.6

39.8

65.2

7.3

 

48

0

50.8

45.1

13.5

48.6

49.3

11.8

46.2

54.2

10.2

43.8

59.6

8.8

41.2

65.7

7.5

 

50

0

52.6

45.5

13.9

50.2

49.8

12.1

47.8

54.7

10.5

45.3

60.2

9.0

42.7

66.3

7.7

 

55

0

57.1

46.6

14.7

54.6

51.0

12.9

52.0

56.0

11.2

49.3

61.5

9.6

46.5

67.7

8.2

 

60

0

61.8

47.7

15.5

59.1

52.2

13.6

56.4

57.3

11.8

53.5

63.0

10.2

50.5

69.2

8.8

 

Table PD-8— 60Ton — CGAF-C60

 

 

 

 

 

 

 

 

Entering Condenser Air Temperature (Degree F)

 

 

 

 

 

 

 

 

 

75.0

 

 

 

85.0

 

 

 

95.0

 

 

 

105.0

 

 

 

115.0

 

LWT

Percent Capacity

System

 

 

Capacity

System

 

Capacity

System

 

 

Capacity

System

 

Capacity

System

 

(Deg F)

Glycol

(Tons)

KW

EER

 

(Tons)

KW

EER

 

(Tons)

KW

EER

 

(Tons)

KW

EER

 

(Tons)

KW

EER

20

28

37.2

50.1

8.9

35.3

55.0

7.7

33.4

60.7

6.6

31.3

67.2

5.6

29.2

74.6

4.7

25

24

41.6

51.3

9.7

39.6

56.4

8.4

37.4

62.2

7.2

35.2

68.8

6.1

32.9

76.3

5.2

30

19

46.4

52.6

10.6

44.1

57.8

9.2

41.8

63.8

7.9

39.4

70.6

6.7

36.8

78.2

5.7

35

14

51.4

54.0

11.4

48.9

59.3

9.9

46.4

65.4

8.5

43.7

72.3

7.3

41.0

80.1

6.1

40

0

57.2

55.6

12.3

54.5

61.1

10.7

51.7

67.3

9.2

48.8

74.4

7.9

45.8

82.2

6.7

42

0

59.2

56.2

12.7

56.5

61.7

11.0

53.6

68.0

9.5

50.6

75.1

8.1

47.5

83.0

6.9

44

0

61.4

56.8

13.0

58.5

62.3

11.3

55.6

68.7

9.7

52.5

75.9

8.3

49.3

83.8

7.1

45

0

62.5

57.1

13.1

59.6

62.7

11.4

56.6

69.1

9.8

53.4

76.2

8.4

50.2

84.2

7.2

46

0

63.6

57.4

13.3

60.6

63.0

11.5

57.6

69.4

9.9

54.4

76.6

8.5

51.1

84.6

7.2

48

0

65.8

58.0

13.6

62.7

63.7

11.8

59.6

70.2

10.2

56.3

77.4

8.7

52.9

85.4

7.4

50

0

68.0

58.6

13.9

64.9

64.4

12.1

61.7

70.9

10.4

58.3

78.2

8.9

54.8

86.3

7.6

55

0

73.8

60.3

14.7

70.4

66.1

12.8

66.9

72.8

11.0

63.3

80.2

9.5

59.6

88.4

8.1

60

0

79.7

62.0

15.4

76.1

68.0

13.4

72.4

74.8

11.6

68.5

82.4

10.0

64.5

90.7

8.5

Notes:

1.Data based on 0.0001 fouling factor at sea level.

2.Interpolation between points is permissible.

3.Extrapolation beyond points is not permissible.

4.EER - Energy Efficiency Ratio (Btu/watt-hour). Power inputs include compressors, water temperatures below 40°F.

5.Ratings based on evaporator drop of 10°F condenser fans and control power

6.Rated in accordance with ARI Standard 550/590-98.

7.Minimum recommended ethylene glycol percentage used for leaving water temperatures below 40°F.

8. Use the following equation to calculate COP values at other than ARI conditions, COP = EER x .2928.

Tons

Model Number

IPLV

COP

10

CGA120B2

12.3

2.9

15

CGA180B

12.9

2.8

20

CGAF-C20

14.8

2.8

25

CGAF-C25

14.6

2.8

30

CGAF-C30

13.9

2.8

40

CGAF-C40

14.9

2.8

50

CGAF-C50

14.5

2.8

60

CGAF-C60

15.0

2.8

Notes:

1. Integrated Part Load Values are EERs in (Btu/watt-hour).

2. CGA120B1 - Single Phase IPLV = 11.4, COP = 2.7

24

CG-PRC007-EN

Page 24