Trane CG-PRC007-EN 30-40Ton, Performance, Data - 60 HZ, Full Load, Table PD-5-30Ton - CGAF-C30

Models: CG-PRC007-EN

1 52
Download 52 pages 16.02 Kb
Page 23
Image 23
(30–40Ton)

Performance

(30–40Ton)

Data — 60 HZ

Full Load

 

 

 

 

Table PD-5— 30Ton — CGAF-C30

 

 

 

 

 

 

 

 

 

Entering Condenser Air Temperature (Degree F)

 

 

 

 

 

 

 

 

 

 

 

 

75.0

 

85.0

 

95.0

 

105.0

 

115.0

 

 

 

LWT

Percent

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

(Deg F)

Glycol

 

(Tons)

KW

EER

 

(Tons)

KW

EER

 

(Tons)

KW

EER

 

(Tons)

KW

EER

 

(Tons)

KW

EER

 

 

20

28

18.8

25.7

8.8

17.9

28.1

7.6

16.9

30.9

6.6

15.9

34.0

5.6

14.9

37.6

4.7

 

25

24

21.0

26.3

9.6

20.0

28.7

8.4

18.9

31.5

7.2

17.8

34.8

6.2

16.7

38.4

5.2

 

30

19

23.3

26.8

10.4

22.2

29.3

9.1

21.1

32.2

7.9

19.9

35.5

6.7

18.7

39.2

5.7

 

35

14

25.8

27.4

11.3

24.6

29.9

9.9

23.4

32.9

8.5

22.1

36.2

7.3

20.8

40.0

6.2

 

40

0

28.7

28.0

12.3

27.4

30.7

10.7

26.1

33.7

9.3

24.7

37.1

8.0

23.2

40.9

6.8

 

42

0

29.7

28.3

12.6

28.4

30.9

11.0

27.0

34.0

9.5

25.6

37.4

8.2

24.1

41.3

7.0

 

44

0

30.8

28.5

13.0

29.5

31.2

11.3

28.0

34.3

9.8

26.6

37.7

8.4

25.0

41.6

7.2

 

45

0

31.4

28.6

13.1

30.0

31.3

11.5

28.5

34.4

9.9

27.0

37.9

8.6

25.5

41.8

7.3

 

46

0

31.9

28.8

13.3

30.5

31.5

11.6

29.0

34.6

10.1

27.5

38.1

8.7

26.0

41.9

7.4

 

48

0

33.0

29.0

13.6

31.6

31.8

11.9

30.1

34.9

10.3

28.5

38.4

8.9

26.9

42.3

7.6

 

50

0

34.1

29.3

14.0

32.7

32.0

12.2

31.1

35.2

10.6

29.5

38.7

9.1

27.9

42.6

7.8

 

55

0

37.0

29.9

14.8

35.5

32.8

13.0

33.8

36.0

11.3

32.1

39.6

9.7

30.3

43.5

8.4

 

60

0

40.1

30.6

15.7

38.4

33.5

13.7

36.6

36.8

11.9

34.8

40.4

10.3

32.9

44.5

8.9

 

Table PD-6 — 40Ton — CGAF-C40

 

 

 

 

 

 

 

 

 

Entering Condenser Air Temperature (Degree F)

 

 

 

 

 

 

 

 

 

 

75.0

 

 

 

85.0

 

 

 

95.0

 

 

 

105.0

 

 

 

115.0

 

LWT

Percent

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

 

Capacity

System

 

(Deg F)

Glycol

 

(Tons)

KW

EER

 

(Tons)

KW

EER

(Tons)

KW

EER

 

(Tons)

KW

EER

 

(Tons)

KW

EER

20

28

23.0

30.9

8.9

21.9

34.1

7.7

 

20.7

37.9

6.6

19.5

42.3

5.5

18.1

47.2

4.6

25

24

25.7

31.7

9.7

24.5

35.0

8.4

 

23.2

38.8

7.2

21.8

43.2

6.1

20.3

48.2

5.1

30

19

28.6

32.5

10.6

27.3

35.8

9.2

 

25.9

39.7

7.8

24.4

44.2

6.6

22.8

49.2

5.5

35

14

31.8

33.3

11.4

30.3

36.7

9.9

 

28.8

40.7

8.5

27.1

45.2

7.2

25.3

50.3

6.0

40

0

35.4

34.3

12.4

33.8

37.8

10.7

 

32.1

41.9

9.2

30.2

46.4

7.8

28.3

51.6

6.6

42

0

36.7

34.7

12.7

35.0

38.2

11.0

 

33.3

42.3

9.4

31.4

46.9

8.0

29.4

52.0

6.8

44

0

38.0

35.0

13.0

36.3

38.6

11.3

 

34.5

42.7

9.7

32.5

47.3

8.2

30.5

52.5

7.0

45

0

38.7

35.2

13.2

36.9

38.8

11.4

 

35.1

42.9

9.8

33.1

47.5

8.4

31.0

52.7

7.1

46

0

39.3

35.4

13.3

37.6

39.0

11.6

 

35.7

43.1

9.9

33.7

47.8

8.5

31.6

53.0

7.2

48

0

40.7

35.8

13.7

38.9

39.4

11.8

 

36.9

43.5

10.2

34.9

48.2

8.7

32.7

53.4

7.3

50

0

42.1

36.2

14.0

40.2

39.8

12.1

 

38.2

44.0

10.4

36.1

48.7

8.9

33.9

53.9

7.5

55

0

45.6

37.2

14.7

43.6

40.9

12.8

 

41.5

45.1

11.0

39.2

49.9

9.4

36.8

55.2

8.0

60

0

49.3

38.2

15.5

47.1

42.0

13.5

 

44.8

46.3

11.6

42.4

51.1

10.0

39.8

56.5

8.5

Notes:

1.Data based on 0.0001 fouling factor at sea level.

2.Interpolation between points is permissible.

3.Extrapolation beyond points is not permissible.

4.EER - Energy Efficiency Ratio (Btu/watt-hour). Power inputs include compressors, water temperatures below 40°F.

5.Ratings based on evaporator drop of 10°F condenser fans and control power

6.Rated in accordance with ARI Standard 550/590-98.

7.Minimum recommended ethylene glycol percentage used for leaving water temperatures below 40°F.

8.Use the following equation to calculate COP values at other than ARI conditions, COP = EER x .2928.

CG-PRC007-EN

23

Page 23
Image 23
Trane CG-PRC007-EN manual 30-40Ton, Performance, Data - 60 HZ, Full Load, Table PD-5-30Ton - CGAF-C30