Table
|
|
|
|
|
|
|
|
|
|
|
|
| External Static Pressure (Pascals) |
|
|
|
|
|
|
|
| ||||
| 25 |
|
|
| 50 | 75 |
|
|
| 100 | 125 | 150 | 175 | 200 | 225 | 250 | |||||||||
m3/h | RPM | kW |
| RPM | kW | RPM | kW | RPM | kW |
| RPM | kW | RPM | kW | RPM | kW | RPM | kW | RPM | kW | RPM | kW | |||
|
|
| 1.12 Nom kW Standard Motor & Low Static Drive |
|
|
|
|
|
| 1.12 Nom kW Standard Motor & Drive |
|
| |||||||||||||
2720 | - | - | 703 | 0.27 | 757 | 0.31 |
|
| 806 | 0.35 | 854 | 0.39 | 899 | 0.43 | 944 | 0.49 | 985 | 0.54 | 1023 | 0.59 | 1060 | 0.64 | |||
3060 | 706 | 0.32 | 760 | 0.35 | 815 | 0.40 |
|
| 861 | 0.45 |
| 904 | 0.49 | 947 | 0.54 | 988 | 0.58 | 1028 | 0.64 | 1067 | 0.70 | 1104 | 0.76 | ||
3400 | 773 | 0.43 | 821 | 0.46 | 873 | 0.51 |
|
| 918 | 0.57 | 958 | 0.62 | 998 | 0.67 | 1036 | 0.71 | 1073 | 0.76 | 1111 | 0.82 | 1147 | 0.89 | |||
3740 |
| 840 | 0.56 | 885 | 0.60 | 930 | 0.65 |
|
| 977 | 0.71 | 1016 | 0.77 | 1053 | 0.82 | 1089 | 0.88 | 1124 | 0.93 | 1158 | 0.98 | 1191 | 1.03 | ||
4080 | 909 | 0.71 | 950 | 0.76 | 990 | 0.80 |
|
| 1034 | 0.87 | 1074 | 0.93 | 1110 | 1.00 | 1143 | 1.06 | 1177 | 1.12 | 1209 | 1.17 | 1241 | 1.23 | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
| External Static Pressure (Pascals) |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
| 275 | 300 | 325 |
|
| 350 | 375 |
|
|
|
|
|
|
|
|
|
| ||||||||
CFM |
| RPM | kW |
| RPM | kW | RPM | kW | RPM | kW |
| RPM | kW |
|
|
|
|
|
|
|
|
|
| ||
|
|
| 1.12 Nom kW Standard Motor & Drive |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
2720 | 1093 | 0.69 | 1126 | 0.74 | 1160 | 0.79 |
|
| 1190 | 0.84 | 1222 | 0.90 |
|
|
|
|
|
|
|
|
|
| |||
3060 | 1138 | 0.82 | 1171 | 0.87 | 1203 | 0.93 |
|
| 1232 | 0.98 |
| 1262 | 1.04 | ← 1.12 Nom kW Standard Motor & |
|
|
|
|
| ||||||
3400 | 1182 | 0.96 | 1215 | 1.02 | 1246 | 1.09 |
|
| 1276 | 1.15 | 1306 | 1.21 | Hi Static Drive |
|
|
|
|
|
|
| |||||
3740 | 1226 | 1.10 |
| 1258 | 1.17 | 1290 | 1.25 |
|
| - | - | - | - |
|
|
|
|
|
|
|
|
|
| ||
4080 | 1272 | 1.29 | - | - | - | - |
|
| - | - | - | - |
|
|
|
|
|
|
|
|
|
| |||
Notes: |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Factory Supplied Motors, In Commercial Equipment, Are |
|
|
| ||||||
Data Includes Pressure Drop Due To Wet Coils And Filters. |
|
|
|
|
|
|
|
| |||||||||||||||||
|
|
|
|
| Definite Purpose Motors, Specifically Designed And |
|
|
|
| ||||||||||||||||
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132 |
|
|
|
|
|
|
|
|
| ||||||||||||||||
|
|
|
|
| Tested To Operate Reliably And Continuously At All |
|
|
|
| ||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Cataloged Conditions. Using The Full Horsepower Range |
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Of Our Fan Motors As Shown In Our Tabular Data Will |
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Not Result In Nuisance Tripping Or Premature Motor |
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Failure. Our Product’s Warranty Will Not Be Affected. |
|
|
|
| |||||
Table |
|
|
|
|
|
|
| ||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
|
|
|
|
|
| External Static Pressure (Inches of Water) |
|
|
|
|
|
|
|
| |||||
| .10 |
| .20 | .30 |
|
|
| .40 | .50 |
| .60 |
| .70 | .80 |
| .90 |
| 1.00 | |||||||
CFM | RPM | BHP |
| RPM | BHP | RPM | BHP | RPM | BHP |
| RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP |
|
|
|
|
|
| |||||||
1600 | - | - | 703 | 0.36 | 757 | 0.41 |
| 806 | 0.47 | 854 | 0.52 | |
1800 | 706 | 0.42 | 760 | 0.47 | 815 | 0.54 |
| 861 | 0.60 |
| 904 | 0.66 |
2000 | 773 | 0.57 | 821 | 0.62 | 873 | 0.69 |
| 918 | 0.76 | 958 | 0.83 | |
2200 | 840 | 0.75 | 885 | 0.80 | 930 | 0.87 |
| 977 | 0.95 | 1016 | 1.03 | |
2400 | 909 | 0.96 | 950 | 1.02 | 990 | 1.08 |
| 1034 | 1.16 | 1074 | 1.25 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
899 | 0.58 | 944 | 0.65 | 985 | 0.73 | 1023 | 0.79 | 1060 | 0.86 |
947 | 0.72 | 988 | 0.78 | 1028 | 0.86 | 1067 | 0.94 | 1104 | 1.02 |
998 | 0.90 | 1036 | 0.96 | 1073 | 1.02 | 1111 | 1.10 | 1147 | 1.19 |
1053 | 1.10 | 1089 | 1.17 | 1124 | 1.24 | 1158 | 1.31 | 1191 | 1.39 |
1110 | 1.34 | 1143 | 1.419 | 1177 | 1.50 | 1209 | 1.57 | 1241 | 1.65 |
|
|
| External Static Pressure (Inches of Water) |
|
|
| |||||
| 1.10 | 1.20 | 1.30 | 1.40 | 1.50 |
| |||||
CFM | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP |
|
|
|
|
|
|
|
| |||||
1600 | 1093 | 0.92 | 1126 | 0.99 | 1160 | 1.06 | 1190 | 1.13 | 1222 | 1.20 |
|
1800 | 1138 | 1.10 | 1171 | 1.17 | 1203 | 1.25 | 1232 | 1.32 | 1262 | 1.39 | ← |
2000 | 1182 | 1.28 | 1215 | 1.37 | 1246 | 1.46 | 1276 | 1.54 | 1306 | 1.62 | Hi Static Drive |
2200 | 1226 | 1.48 | 1258 | 1.57 | 1290 | 1.67 | - | - | - | - |
|
2400 | 1272 | 1.73 | - | - | - | - | - | - | - | - |
|
Notes: |
|
|
|
|
|
|
|
|
|
| Factory Supplied Motors, In Commercial Equipment, Are |
Data Includes Pressure Drop Due To Wet Coils And Filters. |
|
|
|
| |||||||
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451 |
|
|
|
| Definite Purpose Motors, Specifically Designed And | ||||||
|
|
|
|
|
|
|
|
|
|
| Tested To Operate Reliably And Continuously At All |
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.