2.24 Nom kW Standard Motor & Low Static Drive

Performance

Data

Table PD-14 — Belt Drive Evaporator Fan Performance -TSC120AD - Downflow Configuration (SI)

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure (Pascals)

 

 

 

 

 

 

 

 

 

25

 

 

50

 

 

75

 

100

125

150

175

200

225

250

m3/h

RPM

kW

RPM

kW

 

RPM

kW

RPM

kW

 

 

RPM

kW

 

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

 

 

 

2.24 Nom kW Standard Motor & Low Static Drive

 

 

 

 

2.24 Nom kW Standard Motor & Drive

 

 

5440

-

-

-

-

-

-

 

-

-

718

0.72

 

754

0.82

789

0.93

822

1.03

856

1.14

887

1.25

6120

-

-

-

-

-

-

 

731

0.81

764

0.90

 

797

0.99

829

1.10

860

1.22

892

1.34

922

1.46

6800

-

-

715

0.81

747

0.90

 

782

1.01

814

1.11

844

1.21

874

1.32

903

1.44

932

1.56

960

1.69

7480

741

0.95

773

1.04

 

803

1.14

 

834

1.24

864

1.36

894

1.48

922

1.59

948

1.70

975

1.82

1001

1.95

8160

803

1.21

833

1.31

861

1.42

 

887

1.52

916

1.64

945

1.77

972

1.90

997

2.02

1022

2.14

1046

2.27

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure (Pascals)

 

 

 

 

 

 

 

 

 

275

 

300

325

 

350

375

400

425

450

475

500

m3/h

RPM

kW

RPM

kW

 

RPM

kW

RPM

kW

 

 

RPM

kW

 

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

 

 

2.24 Nom kW Standard Motor & Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5440

917

1.36

945

1.47

973

1.60

 

999

1.72

1024

1.84

1048

1.97

1072

2.10

1095

2.23

1117

2.37

1140

3.36

6120

951

1.57

979

1.69

1007

1.82

 

1033

1.94

 

1059

2.07

1082

2.20

1107

2.34

1130

2.49

1152

2.63

1173

3.71

6800

988

1.82

1015

1.95

1042

2.08

 

1068

2.21

 

 

1093

2.35

1117

2.48

1142

2.63

1164

2.76

1187

2.91

1209

4.11

7480

1028

2.09

1053

2.23

1078

2.38

 

1103

2.52

1128

2.66

1152

2.81

1176

2.95

1198

3.10

1221

3.25

-

-

8160

1071

2.41

1095

2.55

1119

2.70

 

1142

2.86

1166

3.02

1189

3.17

1212

3.33

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

2.24 Nom kW Standard Motor & High Static Drive

 

 

 

 

 

 

Notes:

Data Includes Pressure Drop Due To Wet Coils And Filters.

Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To

Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors

2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139

As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty

 

 

Will Not Be Affected.

Table PD-14a — Belt Drive Evaporator Fan Performance -TSC120AD - Downflow Configuration (IP)

 

 

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

 

.10

 

.20

 

 

 

.30

.40

.50

 

 

 

.60

 

 

.70

.80

 

.90

 

1.00

CFM

RPM

BHP

RPM

BHP

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

3 HP Standard Motor & Low Static Drive

 

 

 

 

 

 

 

3 HP Standard Motor & Drive

 

 

3200

 

-

-

-

-

-

-

-

-

718

0.97

 

754

1.10

 

789

1.25

822

1.38

856

1.53

887

1.67

3600

 

-

-

-

-

-

-

731

1.08

764

1.20

 

797

1.33

 

829

1.48

860

1.63

892

1.79

922

1.95

4000

 

-

-

715

1.09

747

1.21

782

1.35

814

1.49

 

844

1.63

 

874

1.77

903

1.93

932

2.09

960

2.27

4400

 

741

1.27

773

1.40

803

1.53

834

1.67

864

1.82

 

894

1.98

 

922

2.13

948

2.28

975

2.44

1001

2.62

4800

 

803

1.62

833

1.76

861

1.90

887

2.04

916

2.20

 

945

2.38

 

972

2.55

997

2.71

1022

2.87

1046

3.04

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

 

1.10

1.20

1.30

1.40

1.50

 

1.60

 

1.70

1.80

1.90

2.00

CFM

RPM

BHP

RPM

BHP

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

3 HP Standard Motor & Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3200

 

917

1.82

945

1.97

973

2.14

999

2.30

1024

2.47

 

1048

2.65

 

1072

2.82

1095

3.00

1117

3.17

1140

3.36

3600

 

951

2.11

979

2.27

1007

2.43

1033

2.60

1059

2.78

 

1082

2.95

 

1107

3.14

1130

3.33

1152

3.52

1173

3.71

4000

 

988

2.44

1015

2.62

1042

2.79

1068

2.97

1093

3.15

 

1117

3.33

 

1142

3.52

1164

3.70

1187

3.91

1209

4.11

4400

 

1028

2.81

1053

3.00

 

1078

3.19

1103

3.38

1128

3.57

 

1152

3.77

 

1176

3.96

1198

4.15

1221

4.36

-

-

4800

 

1071

3.23

1095

3.42

 

1119

3.62

1142

3.83

1166

4.04

 

1189

4.25

 

1212

4.46

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

3 HP Standard Motor & High Static Drive

 

 

 

 

 

 

 

Notes:

Data Includes Pressure Drop Due To Wet Coils And Filters.

Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To

Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors

3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475

As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty

 

 

Will Not Be Affected.