Trane TSC060-120 manual Performance Data, 3400 m3/h

Models: TSC060-120

1 48
Download 48 pages 56.85 Kb
Page 32
Image 32
3400 m3/h

Performance

Data

Table PD-24 — Air Temperature Rise Across Electric Heaters (Degrees C)

kW

 

 

3400 m3/h

4100 m3/h

5100 m3/h

5800 m3/h

6800 m3/h

380V

/ 415V

Voltage

Stages

TSC060AD

TSC072AD

TSC090AD

TSC102AD

TSC120AD

07.5

/ 09.0

380-415/50/3

2

6.6 / 7.9

—-

—-

—-

—-

10.9

/ 13.0

380-415/50/3

2

9.6 / 11.4

—-

—-

—-

—-

11.3

/ 13.5

380-415/50/3

1

—-

8.3

/ 9.9

6.6 / 7.9

—-

—-

14.4

/ 17.2

380-415/50/3

2

12.6 / 15.1

—-

—-

—-

—-

16.9

/ 20.2

380-415/50/3

2

—-

12.4

/ 14.8

9.9 / 11.8

8.7 / 10.4

7.4 / 8.9

22.6

/ 26.9

380-415/50/3

2

—-

16.5

/ 19.7

13.2 / 15.7

11.7 / 13.9

9.9 / 11.8

33.8

/ 40.4

380-415/50/3

2

—-

—-

—-

—-

14.8 / 17.7

Note:

For minimum design airflow, see performance table for each unit.

To calculate temp rise at differrent airflow, use following formula:

Temp. Rise (C0) across Elect Htr = (kW x 2985)/( m3/h)

Table PD-24A — Air Temperature Rise Across Electric Heaters (Degrees F)

kW

 

 

2000 CFM

2400 CFM

3000 CFM

3400 CFM

4000 CFM

380V

/ 415V

Voltage

Stages

TSC060AD

TSC072AD

TSC090AD

TSC102AD

TSC120AD

07.5

/ 09.0

380-415/50/3

2

11.9

/ 14.2

—-

—-

—-

—-

10.9

/ 13.0

380-415/50/3

2

17.2

/ 20.5

—-

—-

—-

—-

11.3

/ 13.5

380-415/50/3

1

—-

14.9 / 17.8

11.9 / 14.2

—-

—-

14.4

/ 17.2

380-415/50/3

2

22.8

/ 27.2

—-

—-

—-

—-

16.9

/ 20.2

380-415/50/3

2

—-

22.3 / 26.6

17.8 / 21.3

15.7 / 18.8

13.4 / 16.0

22.6

/ 26.9

380-415/50/3

2

—-

29.8 / 35.4

23.8 / 28.3

21.0 / 25.0

17.9 / 21.3

33.8

/ 40.4

380-415/50/3

2

—-

—-

—-

—-

26.7 / 31.9

Note:

For minimum design airflow, see performance table for each unit.

To calculate temp rise at differrent airflow, use following formula:

Temp. Rise (F0) across Elect Htr = (kW x 3414)/(1.08 x CFM)

32

RT-PRC016-EN

Page 32
Image 32