Performance
Data
Table
kW |
|
| 3400 m3/h | 4100 m3/h | 5100 m3/h | 5800 m3/h | 6800 m3/h | ||
380V | / 415V | Voltage | Stages | TSC060AD | TSC072AD | TSC090AD | TSC102AD | TSC120AD | |
07.5 | / 09.0 | 2 | 6.6 / 7.9 | ||||||
10.9 | / 13.0 | 2 | 9.6 / 11.4 | ||||||
11.3 | / 13.5 | 1 | 8.3 | / 9.9 | 6.6 / 7.9 | ||||
14.4 | / 17.2 | 2 | 12.6 / 15.1 | ||||||
16.9 | / 20.2 | 2 | 12.4 | / 14.8 | 9.9 / 11.8 | 8.7 / 10.4 | 7.4 / 8.9 | ||
22.6 | / 26.9 | 2 | 16.5 | / 19.7 | 13.2 / 15.7 | 11.7 / 13.9 | 9.9 / 11.8 | ||
33.8 | / 40.4 | 2 | 14.8 / 17.7 |
Note:
For minimum design airflow, see performance table for each unit.
To calculate temp rise at differrent airflow, use following formula:
Temp. Rise (C0) across Elect Htr = (kW x 2985)/( m3/h)
Table
kW |
|
| 2000 CFM | 2400 CFM | 3000 CFM | 3400 CFM | 4000 CFM | ||
380V | / 415V | Voltage | Stages | TSC060AD | TSC072AD | TSC090AD | TSC102AD | TSC120AD | |
07.5 | / 09.0 | 2 | 11.9 | / 14.2 | |||||
10.9 | / 13.0 | 2 | 17.2 | / 20.5 | |||||
11.3 | / 13.5 | 1 | 14.9 / 17.8 | 11.9 / 14.2 | |||||
14.4 | / 17.2 | 2 | 22.8 | / 27.2 | |||||
16.9 | / 20.2 | 2 | 22.3 / 26.6 | 17.8 / 21.3 | 15.7 / 18.8 | 13.4 / 16.0 | |||
22.6 | / 26.9 | 2 | 29.8 / 35.4 | 23.8 / 28.3 | 21.0 / 25.0 | 17.9 / 21.3 | |||
33.8 | / 40.4 | 2 | 26.7 / 31.9 |
Note:
For minimum design airflow, see performance table for each unit.
To calculate temp rise at differrent airflow, use following formula:
Temp. Rise (F0) across Elect Htr = (kW x 3414)/(1.08 x CFM)
32 |