Performance

Data

Table PD-11 — Belt Drive Evaporator Fan Performance -TSC090AD - Horizontal Configuration (SI)

 

 

 

 

 

 

 

 

 

External Static Pressure (Pascals)

 

 

 

 

 

 

 

 

 

 

25

 

50

 

75

100

125

150

175

200

225

250

m3/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

1.50 Nom kW Std Motor & Low Static Drive

 

 

 

 

 

1.50 Nom kW Standard Motor & Drive

 

 

 

 

4080

-

-

673

0.42

718

0.47

769

0.54

814

0.61

855

0.67

893

0.73

929

0.81

965

0.88

999

0.96

4590

702

0.51

738

0.56

773

0.62

817

0.68

862

0.76

904

0.85

941

0.92

975

0.98

1009

1.06

1041

1.14

5100

771

0.68

805

0.74

837

0.81

870

0.87

912

0.94

951

1.03

989

1.12

1025

1.21

1056

1.28

1088

1.36

5610

842

0.89

873

0.96

903

1.03

930

1.10

963

1.17

1000

1.25

1037

1.34

1073

1.45

1106

1.55

1136

1.63

6120

913

1.14

942

1.22

970

1.30

996

1.37

1021

1.45

1052

1.52

1086

1.61

1121

1.71

1153

1.82

1184

1.93

 

1.50 Nom kW Standard Motor & Drive

 

 

 

 

1.50 Nom kW Standard Motor &

 

2.24 Nom kW OS

 

 

 

 

 

 

 

 

 

 

 

 

 

Hi Static Drive

 

 

Motor & Hi Static Drive

External Static Pressure (Pascals)

275300325350375 CFM RPM kW RPM kW RPM kW RPM kW RPM kW

 

 

1.50 Nom kW Standard Motor & Hi Static Drive

 

 

4080

1035

1.04

1070

1.12

1104

1.19

1137

1.27

1168

1.35

4590

1073

1.22

1104

1.31

1136

1.40

1167

1.48

1198

1.57

5100

1117

1.44

1146

1.53

1176

1.62

1205

1.72

1233

1.82

5610

1165

1.72

1194

1.80

1220

1.88

1248

1.98

1275

2.08

6120

1215

2.04

1242

2.13

1269

2.22

1295

2.31

1319

2.40

 

 

2.24 Nom kW Over-Sized Motor & Hi Static Drive

 

 

Notes:

Data Includes Pressure Drop Due To Wet Coils And Filters.

1.50kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464

2.24kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139

Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty Will Not Be Affected.

Table PD-11a — Belt Drive Evaporator Fan Performance -TSC090AD - Horizontal Configuration (IP)

 

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

 

 

 

.10

 

.20

 

 

.30

 

.40

 

.50

 

 

 

 

.60

 

.70

 

.80

 

 

.90

 

1.00

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

2 HP Std Motor & Low Static Drive

 

 

 

 

 

 

 

2 HP Standard Motor & Drive

 

 

 

 

 

 

 

2400

 

-

-

673

0.56

 

718

0.63

769

0.72

814

0.82

 

855

0.90

 

893

0.98

929

1.08

 

965

1.18

999

1.29

2700

 

702

0.68

738

0.76

 

773

0.83

817

0.92

862

1.02

 

904

1.13

 

941

1.23

975

1.32

 

1009

1.42

1041

1.52

3000

 

 

 

 

 

 

837

1.08

870

1.17

912

1.26

 

951

1.38

 

989

1.51

1025

1.62

 

1056

1.72

1088

1.82

771

0.91

805

1.00

 

3300

 

842

1.19

873

1.29

 

903

1.38

930

1.47

963

1.57

 

1000

1.68

 

1037

1.80

1073

1.94

 

1106

2.08

1136

2.19

3600

 

913

1.53

942

1.63

 

970

1.74

996

1.84

1021

1.94

 

 

1052

2.04

 

1086

2.16

1121

2.29

 

1153

2.44

1184

2.59

 

 

2 HP Standard Motor & Drive

 

 

 

 

 

 

 

 

2 HP Std Motor & Hi Static Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 HP Over-Sized Motor

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

 

 

 

 

& Hi Static Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.10

1.20

 

1.30

1.40

1.50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 HP Standard Motor & Hi Static Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2400

 

1035

1.39

1070

1.50

 

1104

1.60

1137

1.70

1168

1.81

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2700

 

1073

1.64

1104

1.76

 

1136

1.87

1167

1.99

1198

2.11

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3000

 

1117

1.93

1146

2.05

 

1176

2.17

1205

2.31

1233

2.44

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3300

 

1165

2.30

1194

2.41

 

1220

2.52

1248

2.66

1275

2.79

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3600

 

1215

2.73

1242

2.86

 

1269

2.98

1295

3.10

1319

3.22

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3 HP Over-Sized Motor & High Static Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Notes:

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data Includes Pressure Drop Due To Wet Coils And Filters.

 

 

 

 

 

Factory Supplied Motors, In Commercial Equipment, Are

 

 

 

2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500

 

 

 

 

 

 

Definite Purpose Motors, Specifically Designed And

 

 

 

 

3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475

 

 

 

 

 

 

Tested To Operate Reliably And Continuously At All

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Cataloged Conditions. Using The Full Horsepower Range

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Of Our Fan Motors As Shown In Our Tabular Data Will

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Not Result In Nuisance Tripping Or Premature Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Failure. Our Product’s Warranty Will Not Be Affected.

 

 

 

 

24

RT-PRC016-EN