Performance
Data
Table
|
|
|
|
|
|
|
|
| External Static Pressure (Pascals) |
|
|
|
|
|
|
|
| ||||
| 25 |
|
| 50 |
| 75 | 100 |
| 125 |
| 150 |
| 175 |
| 200 |
| 225 |
| 250 |
| |
m3/h | RPM | kW | RPM | kW | RPM | kW | RPM | kW |
| RPM | kW | RPM | kW | RPM | kW | RPM | kW | RPM | kW | RPM | kW |
| 1.12 Nom kW Standard Motor & Low Static Drive |
|
|
|
| 1.12 Nom kW Standard Motor & Drive |
|
|
|
| |||||||||||
3260 | - | - | 565 | 0.23 | 627 | 0.29 | 679 | 0.34 |
| 726 | 0.39 | 771 | 0.45 | 814 | 0.51 | 857 | 0.57 | 899 | 0.63 | 939 | 0.70 |
3670 | 566 | 0.26 | 609 | 0.31 | 663 | 0.36 | 716 | 0.42 | 762 | 0.48 | 804 | 0.54 | 843 | 0.60 | 883 | 0.67 | 922 | 0.74 | 960 | 0.81 | |
4080 | 619 | 0.35 | 660 | 0.40 | 701 | 0.45 | 751 | 0.51 | 798 | 0.59 | 839 | 0.65 | 877 | 0.71 | 914 | 0.78 | 950 | 0.85 | 984 | 0.93 | |
4490 | 672 | 0.45 | 710 | 0.51 | 745 | 0.56 | 788 | 0.62 | 833 | 0.69 | 875 | 0.77 | 914 | 0.85 | 949 | 0.91 | 984 | 0.98 | 1016 | 1.06 | |
4890 | 726 | 0.58 | 762 | 0.64 | 795 | 0.70 | 828 | 0.76 | 869 | 0.82 | 911 | 0.91 | 950 | 0.99 | 986 | 1.07 | 1019 | 1.14 | 1051 | 1.22 | |
|
|
| 1.12 Nom kW Standard Motor & Drive |
|
|
|
|
|
|
|
|
| 1.12 Nom kW Standard Motor | ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| & Hi Static Drive |
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
| External Static Pressure (Pascals) |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
| 275 |
| 300 | 325 | 350 | 375 |
|
|
|
|
|
|
|
|
|
| |||||
CFM | RPM | kW | RPM | kW | RPM | kW | RPM | kW |
| RPM | kW |
|
|
|
|
|
|
|
|
|
|
|
|
| 1.12 Nom kW Standard Motor & Hi Static Drive |
|
|
|
|
|
|
|
|
|
|
| |||||||
3260 | 978 | 0.76 | 1015 | 0.83 | 1051 | 0.90 | 1086 | 0.97 | 1118 | 1.04 |
|
|
|
|
|
|
|
|
|
| |
3670 | 996 | 0.87 | 1034 | 0.95 | 1069 | 1.02 | 1103 | 1.09 | 1136 | 1.17 |
|
|
|
|
|
|
|
|
|
| |
4080 | 1020 | 1.00 | 1055 | 1.08 | 1089 | 1.16 | 1122 | 1.23 | 1154 | 1.31 |
|
|
|
|
|
|
|
|
|
| |
4490 | 1049 | 1.14 | 1081 | 1.23 | 1113 | 1.31 | 1144 | 1.40 | 1176 | 1.48 |
|
|
|
|
|
|
|
|
|
| |
4890 | 1081 | 1.30 | 1112 | 1.38 | 1141 | 1.47 | 1170 | 1.57 | 1199 | 1.66 |
|
|
|
|
|
|
|
|
|
| |
|
|
| 1.50 Nom kW |
|
|
|
|
|
|
|
|
|
|
| |||||||
Notes: |
|
|
|
|
|
|
|
|
|
|
| Factory Supplied Motors, In Commercial Equipment, Are |
|
|
| ||||||
Data Includes Pressure Drop Due To Wet Coils And Filters. |
|
|
|
|
| Definite Purpose Motors, Specifically Designed And |
|
|
|
| |||||||||||
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132 |
|
|
|
|
| Tested To Operate Reliably And Continuously At All |
|
|
|
| |||||||||||
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464 |
|
|
|
|
| Cataloged Conditions. Using The Full Horsepower Range |
|
|
|
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product’s Warranty Will Not Be Affected.
Table
|
|
| External Static Pressure (Inches of Water) |
|
|
|
| ||
.10 | .20 | .30 | .40 | .50 | .60 | .70 | .80 | .90 | 1.00 |
CFM RPM BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | RPM BHP | RPM | BHP RPM | BHP RPM BHP | RPM BHP |
1920 | - | - | 565 | 0.31 | 627 | 0.39 |
2160 | 566 | 0.35 | 609 | 0.41 | 663 | 0.48 |
2400 | 619 | 0.47 | 660 | 0.54 | 701 | 0.60 |
2640 | 672 | 0.61 | 710 | 0.68 | 745 | 0.76 |
2880 | 726 | 0.77 | 762 | 0.86 | 795 | 0.94 |
|
|
|
|
|
|
|
|
|
|
| |||||
679 | 0.45 | 726 | 0.52 | 771 | 0.60 | 814 | 0.69 | 857 | 0.77 | 899 | 0.85 | 939 | 0.93 |
716 | 0.57 | 762 | 0.64 | 804 | 0.72 | 843 | 0.80 | 883 | 0.90 | 922 | 0.99 | 960 | 1.08 |
751 | 0.69 | 798 | 0.78 | 839 | 0.87 | 877 | 0.95 | 914 | 1.04 | 950 | 1.14 | 984 | 1.24 |
788 | 0.83 | 833 | 0.93 | 875 | 1.04 | 914 | 1.13 | 949 | 1.22 | 984 | 1.31 | 1016 | 1.42 |
828 | 1.02 | 869 | 1.11 | 911 | 1.21 | 950 | 1.33 | 986 | 1.44 | 1019 | 1.53 | 1051 | 1.63 |
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| External Static Pressure (Inches of Water) |
|
| |||||
| 1.10 | 1.20 | 1.30 | 1.40 | 1.50 | |||||
CFM | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP |
|
|
|
|
| ||||||
1920 | 978 | 1.02 | 1015 | 1.11 | 1051 | 1.20 | 1086 | 1.30 | 1118 | 1.39 |
2160 | 996 | 1.17 | 1034 | 1.27 | 1069 | 1.36 | 1103 | 1.46 | 1136 | 1.56 |
2400 | 1020 | 1.35 | 1055 | 1.45 | 1089 | 1.55 | 1122 | 1.66 | 1154 | 1.76 |
2640 | 1049 | 1.53 | 1081 | 1.65 | 1113 | 1.76 | 1144 | 1.87 | 1176 | 1.98 |
2880 | 1081 | 1.74 | 1112 | 1.86 | 1141 | 1.97 | 1170 | 2.10 | 1199 | 2.22 |
2 HP
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters. | Factory Supplied Motors, In Commercial Equipment, Are | |
Definite Purpose Motors, Specifically Designed And | ||
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451 | ||
Tested To Operate Reliably And Continuously At All | ||
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500 | ||
Cataloged Conditions. Using The Full Horsepower Range | ||
| ||
| Of Our Fan Motors As Shown In Our Tabular Data Will | |
| Not Result In Nuisance Tripping Or Premature Motor | |
| Failure. Our Product’s Warranty Will Not Be Affected. |
22 |