Data

Table PD-9 — Belt Drive Evaporator Fan Performance -TSC072AD - Horizontal Configuration (SI)

 

 

 

 

 

 

 

 

 

External Static Pressure (Pascals)

 

 

 

 

 

 

 

 

 

25

 

 

50

 

75

100

 

125

 

150

 

175

 

200

 

225

 

250

 

m3/h

RPM

kW

RPM

kW

RPM

kW

RPM

kW

 

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

RPM

kW

 

1.12 Nom kW Standard Motor & Low Static Drive

 

 

 

 

1.12 Nom kW Standard Motor & Drive

 

 

 

 

3260

-

-

565

0.23

627

0.29

679

0.34

 

726

0.39

771

0.45

814

0.51

857

0.57

899

0.63

939

0.70

3670

566

0.26

609

0.31

663

0.36

716

0.42

762

0.48

804

0.54

843

0.60

883

0.67

922

0.74

960

0.81

4080

619

0.35

660

0.40

701

0.45

751

0.51

798

0.59

839

0.65

877

0.71

914

0.78

950

0.85

984

0.93

4490

672

0.45

710

0.51

745

0.56

788

0.62

833

0.69

875

0.77

914

0.85

949

0.91

984

0.98

1016

1.06

4890

726

0.58

762

0.64

795

0.70

828

0.76

869

0.82

911

0.91

950

0.99

986

1.07

1019

1.14

1051

1.22

 

 

 

1.12 Nom kW Standard Motor & Drive

 

 

 

 

 

 

 

 

 

1.12 Nom kW Standard Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

& Hi Static Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure (Pascals)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

275

 

300

325

350

375

 

 

 

 

 

 

 

 

 

 

CFM

RPM

kW

RPM

kW

RPM

kW

RPM

kW

 

RPM

kW

 

 

 

 

 

 

 

 

 

 

 

 

 

1.12 Nom kW Standard Motor & Hi Static Drive

 

 

 

 

 

 

 

 

 

 

 

3260

978

0.76

1015

0.83

1051

0.90

1086

0.97

1118

1.04

 

 

 

 

 

 

 

 

 

 

3670

996

0.87

1034

0.95

1069

1.02

1103

1.09

1136

1.17

 

 

 

 

 

 

 

 

 

 

4080

1020

1.00

1055

1.08

1089

1.16

1122

1.23

1154

1.31

 

 

 

 

 

 

 

 

 

 

4490

1049

1.14

1081

1.23

1113

1.31

1144

1.40

1176

1.48

 

 

 

 

 

 

 

 

 

 

4890

1081

1.30

1112

1.38

1141

1.47

1170

1.57

1199

1.66

 

 

 

 

 

 

 

 

 

 

 

 

 

1.50 Nom kW Over-Sized Motor & Hi Static Drive

 

 

 

 

 

 

 

 

 

 

 

Notes:

 

 

 

 

 

 

 

 

 

 

 

Factory Supplied Motors, In Commercial Equipment, Are

 

 

 

Data Includes Pressure Drop Due To Wet Coils And Filters.

 

 

 

 

 

Definite Purpose Motors, Specifically Designed And

 

 

 

 

1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132

 

 

 

 

 

Tested To Operate Reliably And Continuously At All

 

 

 

 

1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464

 

 

 

 

 

Cataloged Conditions. Using The Full Horsepower Range

 

 

 

Of Our Fan Motors As Shown In Our Tabular Data Will

Not Result In Nuisance Tripping Or Premature Motor

Failure. Our Product’s Warranty Will Not Be Affected.

Table PD-9a — Belt Drive Evaporator Fan Performance -TSC072AD - Horizontal Configuration (IP)

 

 

 

External Static Pressure (Inches of Water)

 

 

 

 

.10

.20

.30

.40

.50

.60

.70

.80

.90

1.00

CFM RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM BHP

RPM

BHP RPM

BHP RPM BHP

RPM BHP

1-1/2 HP Standard Motor & Low Static Drive

1920

-

-

565

0.31

627

0.39

2160

566

0.35

609

0.41

663

0.48

2400

619

0.47

660

0.54

701

0.60

2640

672

0.61

710

0.68

745

0.76

2880

726

0.77

762

0.86

795

0.94

 

 

1-1/2 HP Standard Motor & Drive

 

 

 

 

1-1/2 HP Standard Motor & Drive

 

 

 

 

 

679

0.45

726

0.52

771

0.60

814

0.69

857

0.77

899

0.85

939

0.93

716

0.57

762

0.64

804

0.72

843

0.80

883

0.90

922

0.99

960

1.08

751

0.69

798

0.78

839

0.87

877

0.95

914

1.04

950

1.14

984

1.24

788

0.83

833

0.93

875

1.04

914

1.13

949

1.22

984

1.31

1016

1.42

828

1.02

869

1.11

911

1.21

950

1.33

986

1.44

1019

1.53

1051

1.63

 

 

 

 

 

 

 

 

1-1/2 HP Std Motor & Hi Static Drive

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External Static Pressure (Inches of Water)

 

 

 

1.10

1.20

1.30

1.40

1.50

CFM

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

RPM

BHP

 

 

1-1/2 HP Standard Motor & Hi Static Drive

 

 

 

1920

978

1.02

1015

1.11

1051

1.20

1086

1.30

1118

1.39

2160

996

1.17

1034

1.27

1069

1.36

1103

1.46

1136

1.56

2400

1020

1.35

1055

1.45

1089

1.55

1122

1.66

1154

1.76

2640

1049

1.53

1081

1.65

1113

1.76

1144

1.87

1176

1.98

2880

1081

1.74

1112

1.86

1141

1.97

1170

2.10

1199

2.22

2 HP Over-Sized Motor & High Static Drive

Notes:

Data Includes Pressure Drop Due To Wet Coils And Filters.

Factory Supplied Motors, In Commercial Equipment, Are

Definite Purpose Motors, Specifically Designed And

1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451

Tested To Operate Reliably And Continuously At All

2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500

Cataloged Conditions. Using The Full Horsepower Range

 

 

Of Our Fan Motors As Shown In Our Tabular Data Will

 

Not Result In Nuisance Tripping Or Premature Motor

 

Failure. Our Product’s Warranty Will Not Be Affected.

22

RT-PRC016-EN

Page 22
Image 22