Performance
Data
Table
|
|
|
|
|
|
|
|
|
| External Static Pressure (Pascals) |
|
|
|
|
|
|
|
|
|
| ||||
|
| 25 |
|
| 50 | 75 |
| 100 |
| 125 |
| 150 |
| 175 |
| 200 |
| 225 |
|
| 250 |
| ||
m3/h | RPM | kW | RPM | kW | RPM | kW | RPM | kW | RPM | kW |
| RPM | kW | RPM | kW |
| RPM | kW | RPM | kW | RPM | kW | ||
|
| 1.50 Nom kW Std Mtr & Low Static Drive |
|
|
|
|
|
| 1.50 Nom kW Standard Motor & Drive |
|
|
|
| |||||||||||
4620 |
| - | - | - | - | 646 | 0.50 | 689 | 0.58 | 734 | 0.67 | 781 | 0.77 | 826 | 0.88 | 865 | 0.98 | 898 | 1.07 |
| 928 | 1.16 | ||
5200 |
| 616 | 0.51 | 654 | 0.57 | 693 | 0.64 | 735 | 0.73 | 773 | 0.82 | 812 | 0.92 | 855 | 1.03 | 897 | 1.15 | 934 | 1.27 |
| 969 | 1.38 | ||
5780 |
| 675 | 0.68 | 711 | 0.75 | 743 | 0.82 | 781 | 0.91 | 819 | 1.01 | 853 | 1.11 | 886 | 1.21 | 925 | 1.34 | 964 | 1.47 |
| 1000 | 1.60 | ||
6350 |
| 735 | 0.89 | 770 | 0.97 | 799 | 1.04 | 830 | 1.12 | 865 | 1.23 | 899 | 1.34 | 930 | 1.45 |
| 960 | 1.56 | 994 | 1.68 |
| 1028 | 1.82 | |
6930 |
| 796 | 1.14 | 828 | 1.23 | 857 | 1.31 | 883 | 1.39 | 913 | 1.48 |
| 945 | 1.60 | 977 | 1.72 |
| ← | 1.84 | 1034 | 1.96 |
| 1061 | 2.08 |
|
|
|
| |||||||||||||||||||||
|
|
| 1006 |
| ||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
| 1.50 Nom kW Std Mtr |
|
| 2.24 Nom kW |
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
| & High Static Drive |
|
|
| Motor & High Static Drive |
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
| External Static Pressure (Pascals) |
|
|
|
|
|
|
|
|
|
| ||||
|
| 275 |
| 300 | 325 |
| 350 |
| 375 |
| 400 |
| 425 |
| 450 |
| 475 |
|
| 500 |
| |||
m3/h | RPM | kW | RPM | kW | RPM | kW | RPM | kW | RPM | kW |
| RPM | kW | RPM | kW |
| RPM | kW | RPM | kW | RPM | kW | ||
|
|
|
|
|
| 1.50 Nom kW Standard Motor & High Static Drive |
|
|
|
|
|
|
|
|
|
|
| |||||||
4620 |
| 956 | 1.25 | 982 | 1.33 | 1008 | 1.42 | 1033 | 1.51 | 1056 | 1.60 | 1079 | 1.69 | 1102 | 1.78 | 1125 | 1.87 | 1146 | 1.95 |
| 1168 | 2.04 | ||
5200 |
| 999 | 1.49 | 1026 | 1.58 | 1052 | 1.68 | 1078 | 1.78 | 1101 | 1.88 | 1124 | 1.98 | 1146 | 2.08 | 1168 | 2.18 | 1188 | 2.27 |
| 1209 | 2.37 | ||
5780 |
| 1034 | 1.73 | 1067 | 1.86 | 1094 | 1.97 | 1120 | 2.08 | 1145 | 2.20 | 1168 | 2.31 | 1191 | 2.42 | 1213 | 2.53 | 1234 | 2.63 |
| 1254 | 2.74 | ||
6350 |
| 1063 | 1.96 | 1098 | 2.11 | 1129 | 2.26 | 1158 | 2.40 | 1185 | 2.53 | 1210 | 2.66 | 1234 | 2.78 | 1256 | 2.90 | 1278 | 3.03 |
| 1299 | 3.15 | ||
6930 |
| 1093 | 2.23 | 1125 | 2.38 | 1157 | 2.53 | 1188 | 2.70 | 1218 | 2.86 | 1245 | 3.01 | 1273 | 3.16 | 1297 | 3.31 | - | - |
| - | - | ||
|
|
|
|
|
|
|
|
|
| 2.24 Nom kW |
|
|
|
|
|
Notes: | Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To | |
Data Includes Pressure Drop Due To Wet Coils And Filters. | ||
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors | ||
1.50 kW - Fan Motor Heat (kW) = 1.178 x Fan kW + 0.464 | ||
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty | ||
2.24 kW - Fan Motor Heat (kW) = 1.138 x Fan kW + 0.139 | ||
Will Not Be Affected. | ||
|
Table
CFM
2720
3060
3400
3740
4080
CFM
2720
3060
3400
3740
4080
|
|
|
|
|
|
|
|
| External Static Pressure (Inches of Water) |
|
|
|
|
|
|
|
|
| ||||||
| .10 |
| .20 |
| .30 |
| .40 | .50 |
| .60 |
| .70 |
| .80 |
| .90 |
|
| 1.00 | |||||
| RPM | BHP | RPM | BHP | RPM | BHP |
| RPM | BHP | RPM | BHP |
| RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | ||
| 2 HP Std Mtr & Low Static Drive |
|
|
|
|
| 2 HP Standard Motor & Drive |
|
|
|
|
|
|
|
| |||||||||
| - | - | - | - | 646 | 0.67 |
| 689 | 0.78 | 734 | 0.90 | 781 | 1.04 |
| 826 | 1.18 | 865 | 1.31 | 898 | 1.44 |
| 928 | 1.56 | |
| 616 | 0.69 | 654 | 0.77 | 693 | 0.86 | 735 | 0.98 | 773 | 1.10 | 812 | 1.23 |
| 855 | 1.39 | 897 | 1.55 | 934 | 1.70 |
| 969 | 1.85 | ||
| 675 | 0.92 | 711 | 1.01 | 743 | 1.10 | 781 | 1.22 | 819 | 1.36 | 853 | 1.49 |
| 886 | 1.62 | 925 | 1.79 | 964 | 1.97 |
| 1000 | 2.14 | ||
| 735 | 1.20 | 770 | 1.30 | 799 | 1.40 | 830 | 1.51 | 865 | 1.65 | 899 | 1.79 |
| 930 | 1.94 | 960 | 2.09 | 994 | 2.26 |
| 1028 | 2.44 | ||
| 796 | 1.53 | 828 | 1.65 | 857 | 1.76 | 883 | 1.86 | 913 | 1.99 |
| 945 | 2.15 |
| 977 | 2.30 | ←1006 | 2.47 | 1034 | 2.63 |
| 1061 | 2.79 | |
|
|
|
| |||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ← |
| 3 HP |
| ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| 2 HP Std Motor & |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
| Hi Static Drive |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| External Static Pressure (Inches of Water) |
|
|
|
|
|
|
|
|
| ||||||
| 1.10 | 1.20 | 1.30 | 1.40 | 1.50 | 1.60 |
| 1.70 | 1.80 | 1.90 |
| 2.00 | ||||||||||||
| RPM | BHP | RPM | BHP | RPM | BHP |
| RPM | BHP | RPM | BHP |
| RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | RPM | BHP | ||
|
| 2 HP Standard Motor & High Static Drive |
|
|
|
|
|
|
|
| 3 HP |
|
| |||||||||||
| 956 | 1.67 | 982 | 1.79 | 1008 | 1.91 | 1033 | 2.03 | 1056 | 2.14 | 1079 | 2.26 |
| 1102 | 2.38 | 1125 | 2.5 | 1146 | 2.62 |
| 1168 | 2.74 | ||
| 999 | 1.99 | 1026 | 2.12 | 1052 | 2.26 |
| 1078 | 2.39 | 1101 | 2.52 | 1124 | 2.66 |
| 1146 | 2.79 | 1168 | 2.92 | 1188 | 3.05 |
| 1209 | 3.18 | |
| 1034 | 2.32 | 1067 | 2.49 | 1094 | 2.64 | 1120 | 2.79 | 1145 | 2.94 | 1168 | 3.09 |
| 1191 | 3.24 | 1213 | 3.39 | 1234 | 3.53 |
| 1254 | 3.68 | ||
| 1063 | 2.63 | 1098 | 2.84 | 1129 | 3.03 | 1158 | 3.21 | 1185 | 3.39 | 1210 | 3.56 |
| 1234 | 3.73 | 1256 | 3.89 | 1278 | 4.06 |
| 1299 | 4.23 | ||
| 1093 | 2.99 | 1125 | 3.19 | 1157 | 3.40 | 1188 | 3.62 | 1218 | 3.83 | 1245 | 4.03 |
| 1273 | 4.24 | 1297 | 4.44 | - | - |
| - | - |
3 HP
Notes: | Factory Supplied Motors, In Commercial Equipment, Are Definite Purpose Motors, Specifically Designed And Tested To | |
Data Includes Pressure Drop Due To Wet Coils And Filters. | ||
Operate Reliably And Continuously At All Cataloged Conditions. Using The Full Horsepower Range Of Our Fan Motors | ||
2 HP - Fan Motor Heat (MBH) = 3.000 x Fan BHP + 0.500 | ||
As Shown In Our Tabular Data Will Not Result In Nuisance Tripping Or Premature Motor Failure. Our Product’s Warranty | ||
3 HP - Fan Motor Heat (MBH) = 2.900 x Fan BHP + 0.475 | ||
Will Not Be Affected. | ||
|
26 |