Performance
Data
Table
|
|
|
|
| Economizer |
|
|
| Electric Heater |
| |
Unit | Airflow | Standard | Pleated Filters |
| OA/RA Dampers2 |
|
|
| Accessory (kW)3 |
| |
|
|
|
|
| |||||||
100% OA | 100% RA | 100% OA | 100% RA |
|
|
|
| ||||
|
|
|
| ||||||||
Model No. | (m3/h) | Filters1 | (50 mm) | Downflow | Horizontal | 9 | 40 | ||||
TSC060AD | 2720 | 25 | 37 | 30 | 11 | 30 | 4 | 11 | 13 | - | |
| 3400 | 37 | 55 | 46 | 17 | 46 | 6 | 17 | 21 | - | |
| 4080 | 55 | 72 | 64 | 26 | 64 | 9 | 25 | 30 | - | |
TSC072AD | 3260 | 10 | 17 | 25 | 2 | 15 | 5 | - | 5 | - | |
| 4080 | 15 | 22 | 27 | 5 | 20 | 5 | - | 8 | - | |
| 4890 | 22 | 30 | 33 | 10 | 25 | 10 | - | 13 | - | |
TSC090AD | 4080 | 15 | 22 | 27 | 5 | 20 | 5 | - | 8 | - | |
| 5100 | 25 | 32 | 35 | 12 | 30 | 12 | - | 16 | - | |
| 6120 | 35 | 45 | 52 | 17 | 62 | 20 | - | 25 | - | |
TSC102AD | 4620 | 12 | 20 | 31 | 7 | 22 | 10 | - | 6 | - | |
| 5780 | 20 | 27 | 47 | 15 | 45 | 15 | - | 10 | - | |
| 6930 | 30 | 40 | 75 | 17 | 77 | 22 | - | 15 | - | |
TSC120AD | 5440 | 17 | 25 | 42 | 12 | 35 | 12 | - | 9 | 10 | |
| 6800 | 27 | 37 | 65 | 17 | 75 | 20 | - | 14 | 17 | |
| 8160 | 40 | 50 | 85 | 22 | 87 | 25 | - | 20 | 26 |
Notes:
1.Tested with standard filters. The TSC060AD has 25 mm (1 inch) standard fiters. The TSC072AD - 120AD has 50 mm (2 inch) standard filters. The difference in pressure drop should be considered when utilizing optional 50 mm (2 inch) pleated filters.
2.OA = Outside Air and RA = Return Air
3.Nominal kW ratings at 415 V
Table
|
|
|
|
| Economizer |
|
|
| Electric Heater |
| |
|
|
|
|
| OA/RA Dampers2 |
|
|
| Accessory (kW)3 |
| |
Unit | Airflow | Standard | Pleated Filters | 100% OA | 100% RA | 100% OA | 100% RA |
|
|
|
|
|
|
|
| ||||||||
Model No. | (CFM) | Filters1 | (2 inch) | Downflow | Horizontal | 9 | 40 | ||||
TSC060AD | 1600 | 0.10 | 0.15 | 0.12 | 0.04 | 0.12 | 0.01 | 0.045 | 0.053 | - | |
| 2000 | 0.15 | 0.22 | 0.18 | 0.07 | 0.18 | 0.02 | 0.070 | 0.083 | - | |
| 2400 | 0.22 | 0.29 | 0.26 | 0.10 | 0.26 | 0.04 | 0.100 | 0.120 | - | |
TSC072AD | 1920 | 0.04 | 0.07 | 0.10 | 0.01 | 0.06 | 0.02 | - | 0.021 | - | |
| 2400 | 0.06 | 0.09 | 0.11 | 0.02 | 0.08 | 0.02 | - | 0.034 | - | |
| 2880 | 0.09 | 0.12 | 0.13 | 0.04 | 0.10 | 0.04 | - | 0.052 | - | |
TSC090AD | 2400 | 0.06 | 0.09 | 0.11 | 0.02 | 0.08 | 0.02 | - | 0.034 | - | |
| 3000 | 0.10 | 0.13 | 0.14 | 0.05 | 0.12 | 0.05 | - | 0.063 | - | |
| 3600 | 0.14 | 0.18 | 0.21 | 0.07 | 0.25 | 0.08 | - | 0.102 | - | |
TSC102AD | 2720 | 0.05 | 0.08 | 0.12 | 0.03 | 0.09 | 0.04 | - | 0.026 | - | |
| 3400 | 0.08 | 0.11 | 0.19 | 0.06 | 0.18 | 0.06 | - | 0.041 | - | |
| 4080 | 0.12 | 0.16 | 0.30 | 0.07 | 0.31 | 0.09 | - | 0.059 | - | |
TSC120AD | 3200 | 0.07 | 0.10 | 0.17 | 0.05 | 0.14 | 0.05 | - | 0.036 | 0.042 | |
| 4000 | 0.11 | 0.15 | 0.26 | 0.07 | 0.30 | 0.08 | - | 0.056 | 0.070 | |
| 4800 | 0.16 | 0.20 | 0.34 | 0.09 | 0.35 | 0.10 | - | 0.081 | 0.106 |
Notes:
1.Tested with standard filters. The TSC060AD has 25 mm (1 inch) standard fiters. The TSC072AD - 120AD has 50 mm (2 inch) standard filters. The difference in pressure drop should be considered when utilizing optional 50 mm (2 inch) pleated filters.
2.OA = Outside Air and RA = Return Air
3.Nominal kW ratings at 415 V
Table
Capacity)
Nominal | Distribution | Capacity |
Voltage | Voltage | Multipiler |
| 380 | 0.84 |
415 | 400 | 0.93 |
| 415 | 1.00 |
30 |