Mechanical Specifications

General

The units shall be convertible airflow.The operating range shall be between 46°C and -18°C (115°F and 0°F) in cooling as standard from the factory for all units. All units shall be factory assembled, internally wired, fully charged with R-22, and 100 percent run tested to check cooling operation, fan and blower rotation, and control sequence before leaving the factory.Wiring internal to the unit shall be colored and numbered for simplified identification.

Casing

Unit casing shall be constructed of zinc coated, heavy gauge, galvanized steel. Exterior surfaces shall be cleaned, phosphatized, and finished with a weather-resistant baked enamel finish. Cabinet construction shall allow for all maintenance on one side of the unit. Service panels shall have lifting handles and be removed and reinstalled by removing only a single fastener while providing a water and air tight seal. All exposed vertical panels and top covers in the indoor air section shall be insulated with a cleanable foil-faced, fire-retardent permanent, odorless glass fiber material. The base of the unit shall be insulated with 13 mm, 16 kg (1/2 inch, 1 pound) density foil-faced, closed-cell material. All insulation edges shall be either captured or sealed.The unit’s base pan shall have no penetrations within the perimeter of the curb other than the raised 29 mm (11/8 inch high downflow supply/return openings to provide an added water integrity precaution, if the condensate drain backs up.The base of the unit shall have provisions for forklift and crane lifting, with forklift capabilities on three sides of the unit.

UnitTop

The top cover shall be one piece construction or where seams exist, it shall be double-hemmed and gasket- sealed. The ribbed top adds extra strength and prevents water from pooling on unit top.

Filters

One inch, throwaway filters shall be standard on all 5 ton units.The filter rack can be converted to two inch capability. 50 mm (2 inch) filters shall be factory supplied on all 6-10 ton units. Optional 50

mm(2 inch) pleated filters shall be available.

Compressors

All units shall have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps. Motor shall be suction gas-cooled and shall have a voltage utilization range of plus or minus 10 percent of unit nameplate voltage. Internal overloads shall be provided with the scroll compressors. Low and high pressure switches shall be standard.

Refrigerant Circuits

Service pressure ports, and refrigerant line filter driers are factory-installed as standard. An area shall be provided for replacement suction line driers.

Evaporator and Condenser Coils

Internally finned, 8 mm (5/16”) copper tubes mechanically bonded to a configured aluminum plate fin shall be standard. Coils shall be leak tested at the factory to ensure the pressure integrity. The evaporator coil and condenser coil shall be leak tested to 1375 kPa (200 psig) and pressure tested to 3100 kPa (450 psig).The condenser coil shall have a patent pending 1 + 1 + 1 hybrid coil designed with slight gaps for ease of cleaning. A removeable, reversible, double-sloped condensate drain pan with provision for through the base condensate drain is standard.

Outdoor Fans

The outdoor fan shall be direct-drive, statically and dynamically balanced, draw-through in the vertical discharge position. The fan motor shall be permanently lubricated and shall have built-in thermal overload protection.

Indoor Fan

All units shall have belt drive motors. Units with belt drive motors shall have an adjustable idler-arm assembly for quick-adjustment to fan belts and motor sheaves. All motors shall be thermally protected. Oversized motors shall be available for high static operations.

Controls

Unit shall be completely factory-wired with necessary controls and contactor pressure lugs or terminal block for power wiring. Units shall have single point power connection as standard. Unit shall provide an external location for mounting a fused disconnect device.

Microprocessor controls provide for all 24 volt control functions. The resident control algorithms shall make all heating, cooling, and/or ventilating decisions in response to electronic signals from sensors measuring indoor and outdoor temperatures. The control algorithm maintains accurate temperature control, minimizes drift from set point, and provides better building comfort. A centralized Microprocessor shall provide anti-short cycle timing and time delay between compressors to provide a higher level of machine protection.

RT-PRC016-EN

45

Page 45
Image 45
Trane TSC060-120 manual Mechanical Specifications

TSC060-120 specifications

The Trane TSC060-120 is a prominent member of Trane's commercial HVAC (Heating, Ventilation, and Air Conditioning) systems, designed to meet the demands of various applications, from small offices to larger commercial venues. This model is part of Trane’s variable refrigerant flow (VRF) systems, which are known for their energy efficiency and flexibility.

One of the standout features of the TSC060-120 is its capacity range, which allows for cooling and heating capacities between 60,000 to 120,000 BTUs. This makes it suitable for diverse environments, adapting well to fluctuating load requirements. Additionally, the unit is designed with a modular approach, meaning that multiple units can be connected to meet larger capacity needs without sacrificing efficiency.

The Trane TSC060-120 incorporates advanced inverter technology, which helps optimize energy consumption by adjusting the compressor speed based on the real-time thermal load of the building. This results in a significant reduction in energy costs and improved comfort levels for occupants. The unit also features a high-efficiency multi-stage filtration system that not only ensures clean air circulation but also contributes to the overall indoor air quality.

The system utilizes a compact and versatile design, allowing for flexible installation options. Its lightweight structure and smaller footprint make it easier to install in tight spaces while still accommodating a powerful performance. The TSC060-120 is designed for quiet operation, which is crucial for noise-sensitive environments, delivering comfort without disruptive sound levels.

In terms of control and monitoring, the TSC060-120 is compatible with Trane's advanced building management systems. This integration allows facility managers to monitor energy usage, schedule maintenance, and control temperatures remotely, enhancing overall operational efficiency.

Moreover, the unit is built with sustainability in mind, using eco-friendly refrigerants that comply with the latest environmental regulations. This commitment to sustainability not only minimizes the ecological footprint but also positions the Trane TSC060-120 as a forward-thinking choice for businesses looking to enhance their energy strategy.

In summary, the Trane TSC060-120 stands out for its efficiency, flexibility, and advanced technology, making it a solid choice for commercial HVAC applications. With its combination of high performance, advanced control features, and commitment to sustainability, it provides an effective solution for modern climate control needs.