Supported flow-control values are 'Hardware', 'Software' and 'None'.

Supported Protocol Configuration

To ensure remote access to serial port 5 is configured as follows:

Telnet Access LAN

Disabled

SSH Access LAN

Enabled

Raw TCP via LAN

Disabled

You would need to issue the following commands from the command line to set system configuration:

#/bin/config –-set=config.ports.port5.ssh=on

#/bin/config –-del=config.ports.port5.Telnet

#/bin/config –-del=config.ports.port5.tcp

The following command will synchronize the live system with the new configuration.

# /bin/config –-run=serialconfig

Note: “/bin/config” commands can be combined into one command for convenience.

Users

You can add a User to the system from the command line by performing the following instructions:

Determine the total number of existing Users. If you have no existing Users, you can assume this is 0.

# /bin/config –-get=config.users.total

This command should display: config.users.total 1

Note that if you see: config.users.total

This means you have 0 Users configured.