Model
3. INSTALLATION
NOTE
All IT modules are factory
All modules are tagged to indicate the configuration including the sensor module number.
Identify all components during unpacking and install using the factory configuration.
3.1SENSOR MODULE LOCATIONS
Select locations for each sensor module based on the following:
•Modules should be placed close to the potential source of gas.
•Modules should be placed in areas accessible for calibration.
•Sensors should be pointed down and the conduit should include an inverse trap to reduce moisture (condensation) from accumulating in the electronics enclosure.
•Remote calibration fitting
3.2WIRING
3.2.1ANALOG
The
3.2.2MODBUS OPERATION USING
Use a minimum of 18 AWG, 2 conductor for DC power connection. No shield required. In addition use a minimum of 24 AWG, low capacitance, shielded data cable for
3.2.3SENTRY OPERATION USING SMC SENTRY CONNECTION
Use a minimum of 18 AWG,
NOTE:
Be sure to follow all local electric code and safety requirements when installing the
3.2.4 GENERAL
Install conduit as required by local code or construction specifications. When sensor modules are to be multiplexed for Sentry or
•Install splice boxes above each sensor module. Use
•Use Auxiliary Connection Assembly, Model
NOTE
The drain wire of shielded cable must NOT be used as one of the conductors.
Installation and wiring must be in accordance with the National Electrical Code. Temperature
rating of cable wire must be at least 75oC. If cable runs through higher temperature
environments, it must be specified for that environment.
Page: 9