5. CALIBRATION
5.1CALIBRATION FREQUENCY
The manufacturer specifies that sensor modules must be calibrated every 180 days. Periodic functional tests are advisable for critical applications and hostile environments.
The sensor module microprocessor software includes high level self checking algorithms which provide continuous sensor diagnostic and self adjustment. Users may elect to increase calibration periods based on low drift experience during the first two calibration periods.
5.2CALIBRATION PREPARATION
Calibration of the sensor is accomplished by simple menu based steps and application of span gas.
NOTE
If an error is made during any stage of the calibration process, hold the magnet stick at the Switch 1 for 10 seconds. A scrolling display will indicate “Operate Mode” and the sensor module will exit the calibration activity and return to normal operating mode. The calibration procedure can then be restarted.
Calibration must be performed only when the area is known to be clear of combustible gas. If necessary, use a portable instrument to confirm that there is no background combustible gas.
For compliance with Factory Mutual (FM) Approvals, the Sierra Monitor Model
5.2.1 CALIBRATION GAS DELIVERY METHODS
Calibration gas can be delivered to the sensors via the following delivery devices: Model
Model
5.2.2 CALIBRATION PROCEDURE
Table
The procedures requires that the menu “keys” be activated using the magnet stick. Each key press steps through the process of setting the zero value for clean air and then setting the span value.
At each of these steps, apply calibration gas of the value corresponding to the setting accepted on the sensor module display.
5.2.3 SENSOR EXPOSURE TO GAS
Figure
Model
Calibration gas must be delivered to the sensor using the flow rate and duration listed in below:
Model | Gas | Flow | Period |
Until Stable (minimum 3 minutes.) |
NOTE:
Following calibration, the module counts down for 300 seconds. During this time the module is updating its internal memory and it
is very important that its power not be interrupted