Model
| Key Function | Display | Description | Reference | ||
|
|
|
| 0%LEL | Default Display |
|
|
|
|
|
|
|
|
| M | E | Mode | ALMRSET: | Mode Function - Alarms Reset |
|
| S | T |
| |||
| M | E | Mode | CALIB: | Mode Function - Calibrate | or Sub Routine A |
| S | T | ||||
| M | E | Enter | Banner: Apply zero gas, enter <E> when done |
| |
| S | T |
| |||
|
|
|
|
| Operation: Confirm area clear of gas, or apply zero air to sensor. |
|
|
|
|
|
|
|
|
| M | E | Enter | ACK | Zero gas setting acknowledged |
|
| S T |
| ||||
|
|
|
|
| ||
|
|
|
| Banner: Select span, enter <E> when done | use Sub Routine B | |
|
|
|
|
|
|
|
| M | E | Enter | Banner: Apply 50% gas, then enter <E> to calibrate gas sensor |
| |
| S | T |
| |||
|
|
|
| C 0%LEL | Operation: Apply calibration gas. |
|
|
|
|
|
|
|
|
|
|
|
| CXX%LEL | Operation: As gas is applied the reading will increase - wait 3 minutes | use Sub Routine C |
|
|
|
|
|
|
|
| M | E | Enter | Calibration Passed - now remove gas |
| |
| S T |
| ||||
|
|
|
|
| ||
|
|
|
| Operation: Five minute time out before sensor is returned to service. |
| |
|
|
|
|
|
|
|
|
|
|
|
| |
M | E | Mode | (Any) | Operation: Hold magnet over Mode <SW1> for ten seconds to abort |
|
S T | calibration |
| |||
|
|
|
| Banner: Operate mode |
|
|
|
|
|
|
|
|
|
| 0%LEL | Default Display |
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
| Banner: Select span, enter <E> when done |
| |
|
|
|
|
|
|
M | E | Down | Operation: Change Span Gas Value to 25% |
| |
S | T |
| |||
M | E | Down | Operation: User adjustable value |
| |
S | T |
| |||
M | E | Enter | Operation: Ready for user adjustment |
| |
S | T |
| |||
M | E | Up (x5) | Operation: User adjustment to new value 30% |
| |
S | T |
| |||
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
M | E | Enter | Operation: No calibration gas applied, or sensor did not respond |
| |
S | T |
|
| correctly. |
|
|
|
| Operation: Five minute time out before sensor is returned to service. |
| |
|
|
|
|
|
|
|
|
|
| Table | |
|
|
|
| Calibration |
Page: 22