Horizontal Termination

Manual backgroundManual backgroundManual backgroundManual background® DIRECT-VENT GAS FIREPLACE

VDDVF36PN/PP and VDDVF36STN/STP Series

VENTING INSTALLATION

Continued

Horizontal Termination

Configurations

Figures 21 through 23 show different con- figurations for venting with horizontal ter- mination. Each figure includes a chart with vertical minimum/maximum and horizon- tal maximum dimensions which must be met. All connections must be sealed with high temperature silicone sealant as speci- fied in the second warning statement on

Horizontal Venting

Vertical (V)

Horizontal (H)

49.5" min.

15" max.

(45° elbow, 1' vertical pipe, 90° elbow)

61.5" min.

34" max.

73.5" min.

58" max.

85.5" min.

10' max.

102.5" min.

20' max.

UP

45° StarterManual background

Elbow

Required

Note: The 30° Starter Elbow Must Be Discarded and Replaced with a 45° Starter Elbow.

page 7. All horizontal terminations require 1/4" rise per 12" of horizontal run.

Figure 21 - Horizontal Termination Configuration for Rigid Venting Using One 90° Elbow

Horizontal Venting

See information in Figure 21 for

Vertical(V) and UP Horizontal(H) maxi- Manual backgroundManual background

mums and minimums. The same amounts apply for flexible venting.

FGFVK Vent Kit Shown

Figure 22 - Horizontal Termination Using Flexible Venting