® VDVF36P and VDVF36ST Series
VENTING
INSTALLATION
Continued
45° Starter
Elbow
Required
Venting with Two 90° Elbows
Vertical (V1) | Horizontal (H) |
5' min. | 6' max. |
6' min. | 12' max. |
7' min. | 18' max. |
8' min. | 20' max. |
Note: Vertical (V1) +
Vertical (V2) = 20' max.
Figure 30 - Vertical Rigid Venting Configuration Using Two 90° Elbows
45° Starter Elbow
Required
RVF Kit Shown
Vertical Venting
V = 30' max.
Figure 31 - Vertical Rigid Venting Configuration With No Horizontal Run
14 | 105706 |