®

DIRECT-VENT FIREPLACE

VENTING INSTALLATION

Continued

Installing Vent System in a Chase

A chase is a vertical boxlike structure built to enclose venting that runs along the out- side of a building. A chase is not required for such venting.

NOTICE: Treatment of firestops and construction of the chase may vary from building type to build- ing type. These instructions are not substitutes for the require- ments of local building codes. You must follow all local building codes .

Note: When installing in a chase, you should insulate the chase as you would the outside walls of your home. This is especially im- portant in cold climates. Minimum clear- ance between vent pipes and combustible materials such as insulation is 1".

After framing the chase (see Framing and Finishing on pages 4 and 5) install the vent system by following the installation instructions.

INSTALLATION FOR HORIZONTAL TERMINATION

2.Rigid vent pipes and fittings have spe- cial twist-lock connections. Assemble the desired combination of pipe and el- bows to the appliance adaptor with pipe seams oriented towards the wall or floor.

Twist-lock Procedure: The female ends of the pipes and fittings have four locking lugs (indentations). These lugs will slide straight into matching slots on the male ends of adjacent pipes and fit- tings. (All connections must be sealed with high temperature silicone sealant as specified in the second warning on page 7.) Push the pipe sections together and twist one section clockwise approxi-

Snorkel

12"

Minimum

Figure 9 - Snorkel Termination

mately one-quarter turn until the sections are fully locked. See Figure 11. Note: Horizontal runs of vent must be sup- ported every three feet. Use wall straps for this purpose.

Flexible vent pipe must be installed with spacer springs every 12". See Figure 11. All connections must be clamped tightly and sealed with high temperature sili- cone sealant as specified in the second warning on page 7.

 

4" Clamp

Female

7" Clamp

Locking

 

Lugs

 

 

Spacer

 

Spring

Male

4" Flex

Pipe

Slots

 

 

7" Flex

 

Pipe

Rigid Vent Pipe Flexible Vent Pipe

Figure 11 - Vent Pipe Connections

1.Determine the route your horizontal venting will take. Note: The location of the horizontal vent termination on the exterior wall must meet all local and national building codes and must not be easily blocked or obstructed.

WARNING: Do not recess vent terminal into a wall or siding.

Snorkel terminations are available for terminations requiring a vertical rise on the exterior of the building (see Figures 9 and 10). Snorkel kit SVK is also avail- able (see page 15). Follow the same in- stallation procedures as used for stan- dard horizontal terminations. If install- ing the snorkel termination below grade (basement applications), you must pro- vide proper drainage to prevent water from entering the snorkel termination (see Figure 10). Do not back fill around the snorkel termination.

Snorkel

12" Minimum

Adequate

Drainage

Figure 10 - Snorkel Termination with Drainage Pipe

8

106497

Page 8
Image 8
Vanguard Managed Solutions MBDV37, MBDV41 Installation for Horizontal Termination, Installing Vent System in a Chase