Vermont Casting Vermont Castings Jefferson Vent Free Gas Heater, Troubleshooting cont’d, 20003447

Models: JUVSR & JUVSM 3095, 3096, 3097, 3100, 3101, 3102, 3105, 3106, 3107, 3110, 3111, 3112 JUVSR 3096, JUVSM 3096 JUVSR, JUVSM, 3095, 3096, 3097, 3100, 3101, 3102, 3105, 3106, 3107, 3110, 3111, 3112

1 22
Download 22 pages 59.18 Kb
Page 16
Image 16
Troubleshooting cont’d.

Vermont Castings Jefferson Vent Free Gas Heater

Troubleshooting cont’d.

 

 

CONDITION

POSSIBLE CAUSE

SOLUTION

Pilot lights but flame goes out when Control Knob is released.

Fig. 26 Pilot flame is lifting.

Thermopile

Thermo-

Pilot lights but Main Burner does not. couple

1.Control Knob not fully depressed or held in long enough.

2.Gas supply line shut-off valve is not fully open.

3.Thermocouple connection is loose at the Control Valve.

4.Pilot flame does not touch the Thermocouple. (Figs. 26, 27) This can be caused by:

A)Incorrect gas pressure, and/or

B)other conditions that should be identified only by a qualified service technician.

5.Thermocouple is damaged.

6.Control Valve is damaged.

1.Depress Control Knob fully and hold in for a full 30 seconds.

2.Fully open gas supply line shut-off valve.

3.Inspect and tighten securely.

4.A) Contact the local gas company. Inlet supply pressure should be 5” w.c.-8”w.c. for NG (5”w.c.-7”w.c. over 8000 ft. elevation) and 11”w.c.-12”w.c. for LP. Adjust as necessary.

B)Call local gas service techni- cian.

5.Call local gas service technician.

6.Call local gas service technician.

Fig. 27 Pilot flame is weak - does not touch Thermocouple.

Fig. 28 Correct LP Pilot Flame.

Fig. 29

Correct NG Pilot Flame.

Pilot lights but Main Burner does not.

1.Gas supply line shut-off valve is not fully open.

2.Foreign material is blocking Burner ports.

3.Main Burner orifice is clogged.

4.Thermostat or remote switch not activated on JUVS.

5.Bad Thermopile.

1.Fully open gas supply line shut-off valve.

2.Insptect and clear debris away from Burner ports.

3.Call local gas service technician.

4.Set thermostat to higher tempera- ture or check remote switch.

5.Call local gas service technician.

Main Burner shuts off and Pilot

1. Insufficient fresh air.

1. Determine that adequate ventila-

flame goes out while in operation.

 

tion exists to provide sufficient

 

 

fresh air. Open a window or

 

 

provide additional ventilation. (See

 

 

Fresh Air Requirements, Pages 7-

 

 

8)

 

2. Incorrect inlet supply pressure.

2. Contact the local gas company.

 

 

Adjust inlet supply pressure to

 

 

specification: NG; 5”w.c.-8”w.c.

 

 

(5”w.c.-7”w.c. at elevations over

 

 

8000 ft.) LP; 11”w.c.-12”w.c.

16

20003447

Page 16
Image 16