Button | Normal Functions | cont. |
|
| |
CPSM | • Fof - Humidity Management Enhancement: This parameter is normally set at 1. This pa- | |
Mode | rameter should not be adjusted, as it simply provides an OFF cycle time for the fan, during | |
(Cont.) | the compressor OFF cycle. However, the parameter is located within the CPSM as a conve- | |
| nience to the customer, should it need to be adjusted. |
|
| • CCS – Cellar | |
| point between 45°f - 67°f. |
|
| • bLL/Act – Compressor Off or On for Low (bLL) or High (Act) Temperature Alarm: These pa- | |
| rameters are set at “n”. With this parameter set at “n” the refrigeration system will continue | |
| to operate normally, if there is a High or Low temperature Alarm. To change this parameter, | |
| change the setting to “y”, and the compressor/refrigeration system will shut off | during a |
| High or Low temperature Alarm. |
|
| • Con/Cof – Compressor On time (Con) and Off time (Cof) with a Probe 1 failure/Alarm. These | |
| parameters are set at Con 40 min/Cof 10 min. In the event that there is a Probe 1 failure/ | |
| Alarm, the compressor/refrigeration system automatically starts a predetermined ON/OFF | |
| cycle, which is controlled by the Con and the Cof parameters. The customer can adjust | |
| these parameters to maintain the desired Bottle Probe temperature. During a Probe 1 | |
| failure/Alarm, the Bottle Probe temperature can be monitored by pressing the Up or Down | |
| arrow to view the High and Low Temperature History. |
|
| • Hes – Differential for Energy Reduction – This parameter is set at 4, which results in a set | |
| point of 58°f during the Energy Reduction mode. A decrease in this setting will decrease | |
| the set point, and an increase in this feature will increase the set point. |
|
|
| |
AUX | “AUX” indicates the unit is in its | |
| a low temp of 26° and has sustained that temp for a period of five minutes. ( The compres- | |
| sor and condenser fans will turn off, but the evaporator fans will continue to run. Once the | |
| temperature of the evaporator gets back up to 40°, the “AUX” light will deactivate and the | |
| system will revert back to normal operating conditions.) |
|
|
|
|
TROUBLESHOOTING ALARM CODES
Alarm Codes | Cause | Solution |
“P1” | Bottle probe failure | Replace Bottle Probe |
“P1” | Bottle probe Disconnected | Reconnect Bottle Probe |
“P2” | Evaporator Probe Failure | Replace Evaporator Probe |
“HA” | Max Bottle Probe Temp Alarm | Check the set point, lower if needed |
|
| Check the door for a good seal |
|
| Check for sufficient insulation, |
“LA” | Minimum Bottle Probe Temp | Check the set point, raise if needed |
| Alarm |
|
“EA” | External Alarm | Check the display to see which alarm code is causing the alarm. |
|
| Then located the solution and repair. |
“POF” | Keypad locked | Hold “Up” and “Down” buttons for 3 to 5 seconds to disable, |
|
| “PON” should appear once key pad is unlocked |
Page 17