WhisperKool 5000TIR owner manual Alarm Codes, CPSM Mode Cont

Models: 5000TI 5000TIR

1 42
Download 42 pages 612 b
Page 31
Image 31
CPSM Mode (Cont.)

CPSM Mode (Cont.)

CCT - Cellar Pre-Chill Duration: This parameter is set to 6 hours, but can be changed between 0-23.5 hours.

Con/Cof – Compressor On time (Con) and Off time (Cof) with a Probe 1 failure/Alarm. These parameters are set at Con 40 min/Cof 10 min. In the event that there is a Probe 1 failure/Alarm, the compressor/refrigeration system automatically starts a predetermined ON/OFF cycle, which is controlled by the Con and the Cof parameters. The customer can adjust these parameters to maintain the desired Bottle temperature.

 

 

Alarm Codes

 

 

 

 

Message

Cause

 

Solution

“P1”

Bottle Probe is Unplugged

 

Attach Bottle Probe to Unit

 

 

 

Faulty Bottle Probe Connection

 

1. Check Bottle Probe attachment at circular connector

 

 

 

 

 

2. Check Bottle Probe connection at green terminal block on

 

 

 

back of controller

 

Defective Bottle Probe

 

Replace the Bottle Probe

“P2”

Faulty Evaporator Probe

 

Check Evaporator Probe connection at green terminal block on

 

Connection

 

back of controller

 

Defective Evaporator Probe

 

Replace the Evaporator Probe

“HA”

Defective Bottle Probe

 

Replace the Bottle Probe

“LA”

The Bottle Probe is sensing a

 

Allow the room to warm up which will increase the temperature

 

temperature of 4° below the set

 

of the wine

 

point

 

 

 

Defective Bottle Probe

 

Replace the Bottle Probe

“POF”

The keypad is locked

 

Hold “Up” and “Down” buttons for 3 to 5 seconds to disable,

 

 

 

“PON” should appear

Page 31

Page 31
Image 31
WhisperKool 5000TIR owner manual Alarm Codes, CPSM Mode Cont