Installing the Auto Gen Start
975-0082-01-01 2–11
Type 2
Type 2 is a three-wire GlowStop configuration recommended for “three-
wire” generators that don’t require a dedicated preheat signal, such as
Onan generators. In this configuration, the start signal is applied for
longer because the generator does its own preheat and cranking while the
start signal is applied.
Figure 2-4
Type 2 and Type 12 connection diagram
Table 2-3
Type 2 relay and timing preset configurations
Relay 1 mode GlowStop
Relay 3 mode No function
Gen Run signal hold time 0.5 s
Preheat time 0 s
Preheat to crank delay 0 s
Crank time 30 s
Crank retry time 40 s
Shutdown bypass time 0 s
Start tries 3
18
17 START
16
14
13
12 GEN RUN SIGNAL
GROUND
STOP
Relay 1
Relay 2
5A fuse
5A fuse
AGS wiring harness Generator wires
Complete overcurrent protection
not shown. Refer to page 2–6.