Installation
2–12 975-0082-01-01
Type 3
Type 3 is a three-wire GlowStop with shutdown bypass configuration.
The configuration shown in Figure 2-5 uses a shutdown bypass output to
temporarily disable the generator’s low oil pressure shutdown
functionality during cranking. (Generators with this functionality often
have a manual means of disabling it during cranking.)
Figure 2-5
Type 3 connection diagram
Table 2-4
Type 3 relay and timing preset configurations
Relay 1 mode GlowStop/Shutdown bypass
Relay 3 mode Preheat/Shutdown bypass
Gen Run signal hold time 0.5 s
Preheat time 20 s
Preheat to crank delay 0 s
Crank time 15 s
Crank retry time 30 s
Shutdown bypass time 10 s
Start tries 3
PREHEAT
BYPASS SHUTDOWN
STOP
14
13
12 GEN RUN SIGNAL
GROUND
18
17 START
16
Relay 1
Relay 2
5A fuse
5A fuse
Generator wireAGS wiring harness wire
Complete overcurrent protection
not shown. Refer to page 2–6.