Installation
2–18 975-0082-01-01
Type 9
Type 9 is a StartStop mode configuration with shutdown bypass
functionality on relay 3. This configuration is intended for Westerbeke
generators.
Figure 2-10
Type 9 connection diagram
Table 2-10
Type 9 relay and timing preset configurations
Relay 1 mode StartStop
Relay 3 mode Shutdown Bypass
Gen Run signal hold time 0.5 s
Preheat time 0 s
Preheat to crank delay 0 s
Crank time 15 s
Crank retry time 30 s
Shutdown bypass time 5 s
Start tries 3
18
17 START
16
14
13
12 GEN RUN SIGNAL
GROUND
STOP
20
19 PREHEAT & SHUTDOWN BYPASS
12V GENERATOR BATTERY +
Relay 1
Relay 3
Relay 2
5A fuse
5A fuse
5A fuse
AGS wiring harness Generator wires
Complete overcurrent protection
not shown. Refer to page 2–6.